4.1 Unit Allocation

4.1.1 Confirmation of I/O Allocation Information

Input and output relays are allocated.
 Input relays
I/O number
CH0
CH1
CH2
X0
X20
X40
X1
X21
X41
X2
X22
X42
X3
X23
X43
X4
X24
X44
X5
X25
X45
X6
X26
X46
X7
X27
X47
X8
X28
X48
X9
X29
X49
XA
X2A
X4A
XB
X2B
X4B
XC
X2C
X4C
XD
X2D
X4D
XE
X2E
X4E
XF
X2F
X4F
X10
X30
X50
~
~
X19
X39
X59
X1A
X3A
X5A
~
~
X1F
X3F
X5F
(Note 1): The I/O numbers actually allocated are the numbers based on the starting word number allocated to the unit.
Example) When the starting word number for the unit is "10", the operation ready done flag for CH0 is X100.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
CH3
X60
Operation ready done
X61
Counter enable
X62
Count direction
X63
X64
Capture 0 done flag
X65
Capture 1 done flag
External output 0 signal
X66
monitor
External output 1 signal
X67
monitor
X68
Input A signal monitor
X69
Input B signal monitor
X6A
Input Z signal monitor
X6B
Control 0 signal monitor
X6C
Control 1 signal monitor
X6D
Overflow annunciation
X6E
Underflow annunciation
X6F
Error annunciation
X70
Comparison match 0 flag
~
~
Comparison match 9 flag
X79
X7A
Comparison match A flag
~
~
Comparison match F flag
X7F
Flag to indicate the counter operation is ready.
Flag to indicate the counter operation is enabled.
Flag to indicate a count direction.
ON: Forward (Addition) OFF: Reverse
(Subtraction)
Flag to announce that the count value is stored in
capture 0 register.
Flag to announce that the count value is stored in
capture 1 register.
Monitors the output state of external output 0
signal.
Monitors the output state of external output 1
signal.
Monitors the input state of input A signal.
Monitors the input state of input B signal.
Monitors the input state of input Z signal.
Monitors the output state of control 0 signal.
Monitors the output state of control 1 signal.
Flag to announce the occurrence of overflow or
underflow (Enabled for the linear counter only.)
Flag to announce the occurrence of an error.
~
Flag to reflect the results of the band comparison
function or target value match function.
~
Description