Cold Junction Compensation

This is the procedure for turning cold junction compensation
on or off when using input from a thermocouple sensor.
This setting should be left "ON" during normal operation. It
should oly be turned off when cold junction compensation is
being performed externally or you wish to record temperature
differences.
• Range on
: Cold junction compensation on
oFF : Cold junction compensation off

Setting Cold Junction Compensation

Press and hold the
1
mode channel menu ("o o o o P P P P E E E E C C C C h h h h 1 1 1 1 "), then use the
keys to display SET ("S S S S E E E E T T T T C C C C h h h h 6 6 6 6 ").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
Press and hold the
2
keys to display rCJ ("r r r r C C C C J J J J ").
Press the
key, then use the
3
select "oFF" when the bottom part of the display
begins to blink.
Cold junction compensation is turned off.
Press the
key to confirm the setting.
4
Press the
key to return to the operation mode
5
PV display.
key to display the setup
key, then use the
keys to
– 79 –
Chapter
8