PV Input Types

PV input source can be any of the following, including
thermocouples and resistance thermometer bulbs.
Setting
Input Type
0
JPT 100Ω
1
PT100Ω
2
J
3
K
4
R
5
B
6
S
7
T
8
E
9
No function
10
No function
11
No function
12
N
13
PL-II
14
Reserved
15
0V to 5V/0-20mA
16
1V to 5V/4-20mA
Chapter
17
0V to 10V
8
18
2V to 10V
19
0mA to 100mV
• When changing between current input (0-20mA/4-20mA)
Caution
and voltage input (0-5V/1-5V), remove the 250Ω resistor
connected to the terminal block. (Or vice versa.)
• Different types of input (thermocouple/resistance thermometer
bulb/voltage or current input) require different connections to
the terminal block. Check the "Instruction Manual".
Sensor Type
Resistance thermometer bulb
Thermocouple
Voltage/Current Input
Voltage Input

Setting the PV Input Type

This section explains how to change the PV input type with
the example of changing from the factory thermocouple
setting of K to R.
Operation mode
Press and hold the
1
The MV1 of the monitoring mode is displayed.
Press and hold the
2
mode channel menu ("o o o o P P P P E E E E C C C C h h h h 1 1 1 1 "), then use the
keys to display SET ("S S S S E E E E T T T T C C C C h h h h 6 6 6 6 ").
Specify the PV input type.
Press and hold the
3
keys to display PvT ("P P P P v v v v T T T T ").
Press the
4
select 4 when the bottom part of the display
begins to blink.
The PV input type is "R thermocouple".
Press the
5
Press the
6
PV/SV display.
– 74 –
key to display "M M M M v v v v 1 1 1 1 ".
key to display the setup
key, then use the
key, then use the
key to confirm the setting.