to
ON/OFF Control Hysteresis
The following sets the hysteresis during ON/OFF control.
Up to seven types of hysteresis (palettes 1 to 7) can be
recorded. Recorded hysteresis can be recalled from
selected PID number ("P P P P L L L L n n n n 1 1 1 1 ") in the operation menu.
• Range: 0% to 50% FS
Refer to
See "ON/OFF Hysteresis Control" (p. 32) for more information
about ON/OFF control hysteresis.
When PID parameter P = 0, ON/OFF control is used.
Point
Setting ON/OFF Control Hysteresis
The following steps explain how to set ON/OFF hysteresis
Chapter
control using 3.0°C as an example.
5
Press and hold the
1
mode channel menu ("o o o o P P P P E E E E C C C C h h h h 1 1 1 1 ") then use the
keys to display PLT ("P P P P L L L L T T T T C C C C h h h h 3 3 3 3 ").
Refer to
See p. 46 in this chapter for information on how to display
the channel menu.
Press and hold the
2
parameter ("S S S S v v v v 1 1 1 1 "), then use the
display hYS1 ("h h h h Y Y Y Y S S S S 1 1 1 1 ").
Press the
3
set ON/OFF control hysteresis to 3.0 when the
bottom part of the display begins to blink.
The hysteresis is set to 3.0°C.
Press the
4
Press the
5
PV/SV display.
key to display the setup
key to display the SV
key, then use the
key to confirm the setting.
key to return to the operation mode
to
Cooling Proportional Band
Sets the cooling proportional band when dual outputs
are selected. Up to seven types of cooling proportional
band (palettes 1 to 7) can be recorded. Recorded cooling
proportional band can be recalled from selected PID
number ("P P P P L L L L n n n n 1 1 1 1 ") in the operation menu.
• Range: 0.0 to 100.0
Refer to
See "Cooling Proportional Band Coefficient" (p. 33) for more information
about cooling proportional band.
Setting Cooling Proportional Band
The following steps explain how to set cooling proportional
band using 5.0% as an example.
Press and hold the
1
mode channel menu ("o o o o P P P P E E E E C C C C h h h h 1 1 1 1 ") then use the
keys to display PLT ("P P P P L L L L T T T T C C C C h h h h 3 3 3 3 ").
Refer to
Press and hold the
2
parameter ("S S S S v v v v 1 1 1 1 "), then use the
display CoL1 ("C C C C o o o o L L L L 1 1 1 1 ").
keys to
Press
3
cooling proportional band to "5.0".
keys to
The cooling proportional band is set to 5.0.
Press the
4
Press the
5
PV/SV display.
– 48 –
key to display the setup
See p. 46 in this chapter for information on how to display
the channel menu.
key to display the SV
, then use the
key to confirm the setting.
key to return to the operation mode
keys to
keys to set the