Ramp/Soak Command; Activating The Ramp/Soak Command; Auto-Tuning; Running Auto-Tuning - FujiFilm PXG4 Operation Manuals

Pxg series digital controller micro controller x
Table of Contents

Advertisement

Ramp/Soak Command

Switches between ramp/soak states.
The following three conditions are possible.
• "oFF" (stop) : The ramp/soak is stopped.
• "rUn" (run) : The ramp/soak starts.
• "hLd" (hold) : The ramp/soak holds. To release the hold,
select "rUn" again.
The parameter information also changes automatically
depending on the ramp/soak state.
• "GS" (during guaranty soak): PV exceeds the range for
guaranty soak when guaranty soak is on.
• "End" (end) : Ramp/soak ends.
Refer to
See "Chapter 6 Ramp/Soak Parameters" (p. 53) for more information
on ramp/soak.

Activating the Ramp/Soak Command

Press and hold the
1
menu of the setting mode, then use the
keys to display "o o o o P P P P E E E E C C C C h h h h 1 1 1 1 ".
Refer to
See p. 23 in this chapter for information on how to display
the channel menu.
Press and hold the
2
keys to display PrG ("P P P P r r r r G G G G ").
Press the
key, then use the
3
display "r r r r U U U U n n n n " when the bottom section of the
screen begins to blink.
Press the
key to confirm the setting.
4
The ramp/soak function will begin.
Press the
key to return to the PV/SV display
5
of the operation mode.
key to display the channel
key, then use the
keys to
– 25 –

Auto-tuning

Running auto-tuning automatically sets the optimal PID.
• Range oFF : Stop/Finish
on
: Auto-tuning (normal type) starts
Lo
: Auto-tuning (low PV type) starts
There are two types of auto-tuning.
Normal type
Requests PID and starts ON/OFF
operation with SV as the baseline.
Low PV type
Requests PID and ON/OFF operation at
a baseline of SV-10%. Use this setting if
you are trying to prevent overshoot.
ON/OFF control is performed during auto-tuning, so SV may
Caution
be overshot. If you are trying to minimize overshooting, use
low PV auto-tuning.
Refer to
See "Control Methods" (p. 101) for more about auto-tuning.

Running Auto-tuning

Press and hold the
1
menu of the setting mode, then use the
keys to display "o o o o P P P P E E E E C C C C h h h h 1 1 1 1 ".
Refer to
See p. 23 in this chapter for information on how to display
the channel menu.
Press and hold the
2
keys to select AT ("A A A A T T T T ").
Select the type of auto-tuning.
Press the
key, then use the
3
display "o o o o n n n n " when the bottom part of the display
begins to blink.
This selects normal auto-tuning.
Press the
key to confirm the setting.
4
Auto-tuning begins.
Press the
key to return to the PV/SV display
5
of the operation mode.
key to display the channel
key, then use the
keys to
A decimal point will blink in the bottom
of the display during auto-tuning.
Chapter
3

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Pxg9Pxg5

Table of Contents