Overview of Monitor Parameters (Ch5)

The monitor allows you to verify the current input and output conditions of the controller.
The monitor can display the following items.
These parameters are displayed only. The settings cannot be changed in these parameters.
Display
Parameter name
"
STAT
" (STAT)
Ramp/soak
progress
"
Mv1
" (Mv1)
Control Output
Display (MV1)
"
Mv2
" (Mv2)
Control Output
Display (MV2)
PFb
"
" (PFb)
PFB Input Value
Display
"
rSv
"(rSv)
RSV Input Value
Display
"
CT1
" (CT1)
Heater current
LC1
"
" (LC1)
Leak current
Chapter
"
TM1
" (TM1)
Remaining time on
7
timer 1
"
TM2
" (TM2)
Remaining time on
timer 2
TM3
"
" (TM3)
Remaining time on
timer 3
"
TM4
" (TM4)
Remaining time on
timer 4
"
TM5
" (TM5)
Remaining time on
timer 5
"
FALT
" (FALT)
Error source display
"
PLno
"(PLno)
Current palette No.
"
PTno
"(PTno)
Current pattern No.
Note 1: Displays when the sixth digit is A, C, E, or P. (Standard type only).
Note 2: Displays when the fifth digit of the model number is V.
Note 3: Displays when the seventh number of the model number is H, K, E, or 2, or the eleventh digit is D (RSV included).
Note 4: Displays when the seventh number of the model number is G or J, or the eleventh digit is A (CT included).
Note 5: Displays depending on the ninth digit and eleventh digit of the model code.
Note 6: The parameters in the shaded area indicates the industrial values.
Function
Displays the progress of the ramp/soak
Displays the output value of the control
output (OUT1).
Displays the output value of the control
output (OUT2) (during dual control).
Displays the input value of the position
feedback
Displays the input value for RSV.
Displays the heater current
Displays the leak current
Displays the remaining time on timer 1
Displays the remaining time on timer 2
Displays the remaining time on timer 3
Displays the remaining time on timer 4
Displays the remaining time on timer 5
Displays the source of an error
Displays the PID palette No. currently
selected.
Displays the pattern No. of the ramp
soak currently selected.
– 64 –
range
oFF (ramp/soak is stopped)
1-rP (Step 1 Ramp)
1-Sk (Step 1 Soak)
16rP (Step 16 Ramp)
16Sk (Step 16 Soak)
End (ramp/soak is finished)
-3.0% to 103.0%
-3.0% to 103.0%
-3.0% to 103.0%
-5% to 105% FS
0A, 0.4A to 50.0A
0A, 0.4A to 50.0A
0 sec to 9999 sec / 0 min to 9999 min
0 sec to 9999 sec / 0 min to 9999 min
0 sec to 9999 sec / 0 min to 9999 min
0 sec to 9999 sec / 0 min to 9999 min
0 sec to 9999 sec / 0 min to 9999 min
FALT=□□0□
0bit :PFB input underflow
1bit :PFB input overflow
8bit : PV input underflow
9bit : PV input overflow
10bit: underrange
11bit: overrange
12bit: RSV underrange
13bit: RSV overrange
14bit: range setting error
15bit: EEPROM error
0 to 7
0 to 6
Remarks
Page
65
65
Note 1
Note 2
66
Note 3
66
Note 4
67
Note 4
67
Note 5
68
Note 5
Note 5
Note 5
Note 5
68
69