Proportional Band, Integration Time, Derivative Time

Specifies PID (Proportional Band, Integration Time,
Derivative Time)
• Range P : 0.0% to 999.9%
I : 0 sec to 3200 sec
D : 0.0 sec to 999.9 sec
The following control methods are available with PID settings.
ON/OFF
When PID parameter P = 0, ON/OFF control is
(2 position)
used, regardless of the values for I and D. Use
control
this function when you want to add simple
controls without worrying about the
controllability.
PID Control
Use this function when you want to control with
high controllability. Operates when P ≠ 0, I ≠ 0,
and D ≠ 0, but P, I, and D must be adjusted to
optimal values for the control target. In normal
situations, run auto-tuning to optimally adjust P,
I, and D before using this function.
PI Control
When P ≠ 0, I ≠ 0, and D = 0, D control is turned
off and PI control is used.
P Control
In principle, P control generates no offset and
PV does not always equal SV. In this situation,
adjust the output convergence value "bAL".
• Running auto-tuning automatically sets PID.
Point
See "Auto-Tuning" (p. xx) for more information.
• The PID settings used during auto-tuning are the
optimal
settings.
responsiveness, adjust PID manually.
• Control normally becomes unstable when "P" is set too
small. On the other hand, setting it too big makes the
response slow.
• Set the hysteresis for the on/off control (2 state) with
the parameter "hyS".
Do not activate auto-tuning when using ON/OFF (2 state)
Caution
control.
If
you
wish
to
change
the
– 31 –

Setting PID

The following steps will explain how to set PID values, using
as an example P=10.0%, I=100 sec and D=20 sec.
Operation mode
Press and hold the
1
MV1 of the monitoring mode is displayed.
Press and hold the
2
mode channel menu ("o o o o P P P P E E E E C C C C h h h h 1 1 1 1 "), then use the
keys to display Pid ("P P P P i i i i d d d d C C C C h h h h 2 2 2 2 ").
Specify the PID.
Press and hold the
3
keys to display P ("P P P P ").
Specify P (Proportional Band)
Press the
key, then use the
4
set P to "10.0".
when the bottom part of the display begins to blink.
Press the
key to confirm the setting.
5
Repeat steps 3-5 (excluding pressing and holding
6
the
key) for I and D.
Press the
key to return to the operation mode
7
PV/SV display.
key to display "M M M M v v v v 1 1 1 1 ".
key to display the setup
key, then use the
keys to
Chapter
4

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Pxg9Pxg5

Table of Contents