PV Input Lower Limit
PV Input Upper Limit
This is the procedure for specifying the upper and lower
limits of PV input. PV input can be set to any value within
these bounds.
• Range: -1999% to 9999%
PV input
1200°C
Possible range for
setting upper/lower limit
0°C

Setting PV Input Upper/Lower Limits

The following steps explain how to set PV input limits by using an
upper limit of 1000°C and a lower limit of 200°C as an example.
Press and hold the
1
mode channel menu ("o o o o P P P P E E E E C C C C h h h h 1 1 1 1 "), then use the
keys to display SET ("S S S S E E E E T T T T C C C C h h h h 6 6 6 6 ").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
Press and hold the
2
keys to display Pvb ("P P P P v v v v b b b b ").
Press the
key, then use the
3
select 200.0 when the bottom part of the display
begins to blink.
The PV input lower limit is set to 200°C.
Press the
key to confirm the setting.
4
Repeat steps 2-4 (excluding pressing and holding
5
the
key) to set the PV input upper limit PvF
("P P P P v v v v F F F F ") to 1000°C.
Press the
key to return to the operation
6
mode PV/SV display.
The value for each sensor can be set to exceed the possible
Caution
measurement range, but accuracy is not guaranteed in these
cases.
,
1000°C
200°C
key to display the setup
key, then use the
keys to
– 75 –

Decimal Place

This is the procedure for setting the decimal place in the
PV display.
• Range
0: No decimal place
1: One decimal place
2: Two decimal places
• Two decimal places are available only when the input is
Point
voltage/current.
• When using one decimal place display for temperature
input, the decimal place will not be displayed for
temperatures of 1000°C and over.

Setting the Decimal Place

The following steps explain how to set the decimal place by
using one decimal place as an example.
Press and hold the
1
mode channel menu ("o o o o P P P P E E E E C C C C h h h h 1 1 1 1 "), then use the
keys to display SET ("S S S S E E E E T T T T C C C C h h h h 6 6 6 6 ").
Refer to
See p. 74 in this chapter for information on how to display
the operation menu.
Press and hold the
2
keys to display Pvd ("P P P P v v v v d d d d ").
Press the
key, then use the
3
select 1 when the bottom part of the display begins
to blink.
The decimal place is now set to one decimal place.
Press the
key to confirm the setting.
4
Press the
key to return to the operation mode
5
PV/SV display.
one decimal place
two decimal places
key to display the setup
key, then use the
keys to
Chapter
8