Siemens SIMATIC ET 200SP Manual page 74

Fail-safe modul f-cm as-i safety st 3rk7136-6sc00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Assigning parameters / Setting the address space
6.4 Data records for diagnostics
Byte.Bit
Description
0.6
Sequence error, channel status 1/0
0.7
Sequence error, channel status 1/1
1.0
Input slave missing or of the
incorrect type
1.1
Control unit of the output switching
group not in cyclic data exchange
1.2
Code sequence error (systematic
fault)
1.3
Code sequence missing in the
memory of the F-CM
1.4
ASIsafe code sequences duplicated 1057
1.5
Sporadic code sequence error
1.6 ... 1.7
Reserved
2.0
Safety sensor triggered
2.1
Switch-on condition not met
2.2
Startup test necessary
2.3
Status of process image (user data) -
2.4
Value status
2.5... 2.7
Reserved
3.0
Safe AS-i input slave configured
3.1
Safe AS-i output slave configured
3.2
Unsafe slave detected
3.3
Safe slave detected, type unknown
3.4
Safe slave detected, type input
slave
3.5
Safe slave detected, type output
slave
3.6
Slave is located in cyclic data
exchange
3.7
Reserved
74
FW V1.0.1 and
Remark
higher: Error
code (decimal) in
the diagnostic
alarm
1046
When the error occurs, the pair of channels at input
1 has the status "1" and at input 2 the status "0".
1047
When the error occurs, the pair of channels at input
1 has the status "1" and at input 2 the status "1".
1050
-
1051
The AS-i master does not address the configured
AS-i address of the output switching group.
1054
Permanent interruption to code sequence, e.g. due
to electromagnetic interference on the sensor cable
or code sequence corruption after replacement of
the safe input module.
1056
-
Identical code sequence occurs several times
1058
Momentary interruption to code sequence, e.g. due
to electromagnetic interference on the sensor
cable.
-
-
-
-
The safe input value has been reset to the status
"0"
-
Test of the input is necessary: Both inputs of the
channel pair must assume the status "0".
-
-
Value status = 1: A valid process value is output for
the channel.
Value status = 0: A substitute value is output for the
channel (error on channel or the channel is
deactivated).
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-