Siemens SIMATIC ET 200SP Manual page 70

Fail-safe modul f-cm as-i safety st 3rk7136-6sc00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Assigning parameters / Setting the address space
6.4 Data records for diagnostics
The following applies for diagnostic alarms of the F-CM AS-i Safety ST module with firmware
V1.0.1 or higher:
● The "Error code" column in the table below indicates which events are relevant here.
● If the associated bit changes in the data record, a diagnostic alarm with the indicated
error code is generated (incoming alarm when bit changes to value "1" and outgoing
alarm when bit changes to value "0").
● If no error code is specified ("-"), a diagnostic alarm is not generated.
● The diagnostic alarms for firmware V1.0.0 are described in Section "DS 92 Device-
specific diagnosis (Page 57)".
Table 6- 14
DS 206 Diagnosis
Byte.Bit
Description
In the case of binary values, the
description declares the status "1"
0
Version High
1
Version Low
2.0
Overtemperature
2.1
Undertemperature
2.2
Incorrect parameter value
2.3
Incorrect or inconsistent firmware
2.4
Supply voltage too high
2.5
Supply voltage too low
2.6
Program cycle time exceeded
2.7
Device fault
3.0
Serious device fault
3.1
Teaching necessary
3.2
Normal operation
3.3
Startup
3.4
Serious device fault
3.5
I/O device signal error
3.6
Code sequence cannot be read
correctly
3.7
Reintegration necessary
4.0
Access to device settings
70
FW V1.0.1 and
Remark
higher: Error
code (decimal) in
the diagnostic
alarm
-
-
-
-
1048
Maximum operating temperature exceeded
786
Ambient temperature too low
16
Configuration data contains errors
283
Firmware is faulty
Firmware update necessary
1038
AS-i voltage too high
1039
AS-i voltage too low
259
Internal cycle time exceeded
1059
Self-test has determined a device fault.
For details, see further error messages.
9
Serious device fault. No communication possible
1055
New code tables are available for transfer.
-
Cyclic I/O data exchange active
-
Parameters are loaded
No cyclic I/O data exchange
-
Serious device fault. No communication possible
-
One or more channels are passivated
-
A code sequence is non-existent or incomplete
-
Error is cleared, but at least one channel is still
passivated
-
Assignment of the F-address
Acceptance of the code sequences
Firmware update
Fail-safe Module F‑CM AS‑i Safety ST (3RK7136‑6SC00‑0BC1)
Manual, 03/2017, A5E03957059020A/RS-AB/002