Siemens SIMATIC ET 200SP Manual page 63

Fail-safe modul f-cm as-i safety st 3rk7136-6sc00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Byte.Bit
Description
62.5
F_CRC_Length
62.6
F_Par_Version
62.7
CRC1 error
63.0 ... 63.2
Reserved
63.3
iPAR_CRC error
63.4
Operator acknowledge requested
63.5 ... 63.7
Reserved
64 ... 65
Reserved
70 ... 89
Reserved
90 ... 91
Object_Code_Sequence_Logic
92 ... 93
Reserved
94 ... 95
Object_input_triggered
96 ... 199
Reserved
Fail-safe Module F‑CM AS‑i Safety ST (3RK7136‑6SC00‑0BC1)
Manual, 03/2017, A5E03957059020A/RS-AB/002
Assigning parameters / Setting the address space
Only with firmware V1.0.0:
Error code (decimal) in the
diagnostic alarm
24 ("Switch-off")
19 ("Communication error")
69 ("Parameter
'F_CRC_Length' does not
match ...")
24 ("Switch-off")
19 ("Communication error")
70 ("Incorrect F-parameter
version or F_Block_ID")
24 ("Switch-off")
19 ("Communication error")
71 ("CRC1 error")
-
24 ("Switch-off")
19 ("Communication error")
75 ("Inconsistent I-parameters
[iParCRC error]")
-
-
-
-
-
-
-
-
6.4 Data records for diagnostics
Remark
F_CRC_Length value does not
match the actual CRC length.
F_Par_Version does not match the
F-parameter set or F-Block_ID is
invalid Block_ID
-
-
-
Channel is ready for reintegration
-
-
-
AS-i address of the first safe
AS-i slave for which a code
sequence error or logic error i
present. See also bit 18.0.
0 = No error
0
= No error
1 ... 31
= AS-i slave address
≥32
= Internal error
numbers
-
AS-i address of the first safe AS-
i slave for which the input_triggered
message is present. See also
bit 18.2.
0
= No error
1 ... 31
= AS-i slave address
≥32
= Internal error
numbers
-
63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents