Siemens SIMATIC ET 200SP Manual page 59

Fail-safe modul f-cm as-i safety st 3rk7136-6sc00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Byte.Bit
Description
12.5 ... 12.7
Reserved
13.0
Reserved
13.1
Device fault
13.2
Parameter assignment error
13.3
Process signal error
13.4
Code sequence error
13.5
Logic error
13.6 ... 13.7
Reserved
14.0
Downloading of module parameters is
not yet complete
14.1
Reserved
14.2
Cyclic data exchange is active
14.3 ... 14.7
Reserved
15 ... 17
Reserved
18.0
Group error code sequence_Logic
18.1
Reserved
18.2
Group_Message_Input_Triggered
18.3 ... 18.7
Reserved
Fail-safe Module F‑CM AS‑i Safety ST (3RK7136‑6SC00‑0BC1)
Manual, 03/2017, A5E03957059020A/RS-AB/002
Assigning parameters / Setting the address space
Only with firmware V1.0.0:
Error code (decimal) in the
diagnostic alarm
-
-
24 ("Switch-off")
27 ("Unclear error")
24 ("Switch-off")
16 ("Parameter assignment
error")
24 ("Switch-off")
27 ("Unclear error")
24 ("Switch-off")
26 ("External error")
24 ("Switch-off")
25 ("Safety-related switch-
off")
-
-
-
-
-
-
24 ("Switch-off")
-
-
-
6.4 Data records for diagnostics
Remark
-
-
See Section Error statuses
(Page 17)
Parameter not permitted in
configuration.
See Section Error statuses
(Page 17)
A code sequence error can occur,
for example, in case of:
Cross-circuit at the inputs
EMC problem
Bit 18.0 is additionally set.
A logic error can occur, for
example, in case of:
Discrepancy error
Sequence error
Bit 18.0 is additionally set.
-
-
-
-
-
-
A code sequence error or logic
error is present for at least one safe
input.
Bytes 90 ... 91 contain the AS-i
address of the first safe input for
which the error is present.
-
At least one monitored safe input
has value status "0".
Possible cause:
Startup test necessary
Safety sensor triggered
Bytes 94 ... 95 contain the
AS-i address of the first safe input
for which the value status "0" is
present.
-
59