Siemens SIMATIC ET 200SP Manual page 62

Fail-safe modul f-cm as-i safety st 3rk7136-6sc00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Assigning parameters / Setting the address space
6.4 Data records for diagnostics
Byte.Bit
Description
49.5
ASIsafe code sequence teaching
active
49.6 ... 49.7
Reserved
50
Code sequence error object
51 ... 54
Reserved
55
Switching group error object
56 ... 61
Reserved
62.0
F_Dest_Adr does not match
62.1
F_Dest_Adr invalid
62.2
F_Source_Adr invalid
62.3
F_WD-Time_0
62.4
F_SIL value
62
Only with firmware V1.0.0:
Error code (decimal) in the
diagnostic alarm
-
-
-
-
-
-
24 ("Switch-off")
19 ("Communication error")
64 ("Different destination
address")
24 ("Switch-off")
19 ("Communication error")
65 ("Invalid destination
address")
24 ("Switch-off")
19 ("Communication error")
66 ("Invalid source address")
24 ("Switch-off")
19 ("Communication error")
67 ("Watchdog time is 0 ms")
24 ("Switch-off")
19 ("Communication error")
68 ("Parameter 'F_SIL'
exceeds the appl. SIL")
Fail-safe Module F‑CM AS‑i Safety ST (3RK7136‑6SC00‑0BC1)
Manual, 03/2017, A5E03957059020A/RS-AB/002
Remark
The code sequences are being
collected. When the code sequen-
ces for all safe AS-i input slaves
detected on the bus are taught, this
bit is reset.
-
This bit contains the lowest
AS-i address for which a code
sequence problem has occurred.
Code sequence problems are:
49.0 ASIsafe code sequences
missing (Prio 3)
49.1 ASIsafe code sequences
duplicated (Prio 1)
49.2 ASIsafe code sequences
new (Prio 4)
49.4 ASIsafe code sequence
error (Prio 2)
-
This byte contains the lowest
AS-i address that is configured for
an output switching group but is not
addressed by the master. Correct
the slave configuration of the
master.
-
-
The coding element does not
contain an F-address.
-
F_WD-Time value is 0 ms.
F_SIL value exceeds SIL value of
the specified device application

Hide quick links: