Cooling System Specifications For 4002-Y2A; Power Supply And Fan Tray Labels For 4002-Y2A - IBM 4002-Y2A Installation And User Manual

Ibm y-series of ethernet switches
Table of Contents

Advertisement

For the 4002-Y2A and 4002-Y4A models, the air flows from the front to the back of
the device. For the 4002-Y2C and 4002-Y4C models, the air flows from the back to
the front of the device.
Note: Operating noise is based on the ISO 7779 standard.
Figure 37 on page 51 shows the airflow for the 4002-Y2B and 4002-Y4B models.
Figure 38 on page 51 shows airflow for 4002-Y2A and 4002-Y4A devices. Figure 39
on page 52 shows the airflow for the 4002-Y2C and 4002-Y4C models.
Attention: For the 4002-Y2A, Y4A, Y2C, and Y4C devices, be sure that the airflow
direction of the power supply unit matches that of the installed fan tray. The
power supplies and fan trays are clearly labeled with an arrow with an "E"or "I",
as shown in Table 27.
50
Ethernet y-series Installation and User Guide: Installation and User Guide
Table 25. Cooling system specifications for 4002-Y2B and 4002-Y4B switches (continued)
Total air flow
200 LFM
Operating noise
ideal 51 dB-A
Table 26. Cooling system specifications for 4002-Y2A, Y4A, Y2C, and Y4C model switches
Total cooling
180 watts
capacity
Total air flow
1152 LFM
Operating noise
ideal 60 dB-A
Table 27. Power supply and fan tray labels for 4002-Y2A ,Y4A, Y2C, and Y4C devices
Devices
4002-Y2A and 4002-Y4A
4002-Y2C and 4002-Y4C
Label on required power
supply
4002-Y2A and Y4A power
supply airflow label
ATTENTION
Power supply and
fan FRU airflow
E
must be the
same to prevent
overheating.
AIRFLOW
4002-Y2C and Y4C power
supply airflow label
ATTENTION
Power supply and
fan FRU airflow
must be the
same to prevent
overheating.
AIRFLOW
Label on required fan
tray
4002-Y2A and Y4A fan
tray airflow label
E
AIRFLOW
4002-Y2C and Y4C fan
tray airflow label
AIRFLOW