Table 4: Cable Cross Section (Cu): 0.5 – 1.5 mm
Terminal
Blocks
1
+10V
2
AI1
3
GND
6
24V
7
DI-C
8
DI1
9
DI2
10
DI3
4
AI2
5
GND
13
DO–
14
DI4
15
DI5
16
DI6
18
AO
20
DO+
A
A
B
B
22
R13
23
R14
24
R22
25
R21
26
R24
Programmable function (
MN04020002E
Signal
Output nominal voltage —
Analog signal input 1
Reference potential
Control voltage for
DI1 – DI6, output (+24V)
Reference potential of
digital inputs DI1 – DI6
Digital input 1
Digital input 2
Digital input 3
Analog input 2
Reference potential
Digital output
Digital input 4
Digital input 5
Digital input 6
Analog output
Digital output
RS-485 signal A
RS-485 signal B
Relay 1, normally open
contact
Relay 1, normally open
contact
Relay 2, normally closed
contact
Relay 2, common
contact
Relay 2, normally open
contact
section "List of parameters," Page 30).
For more information visit: www.eaton.com
M-Max Series adjustable frequency drive
2
Factory Setting
Frequency reference value
LOGIC– (GND)
FWD start enable, forward
REV start enable, reverse
Fixed frequency B0
PI actual value
Active = READY
Fixed frequency B1
Error acknowledgment
PI controller deactivated
Output frequency
Supply voltage,
see terminal 13
BUS-Communication
BUS-Communication
Active = RUN
Active = RUN
Active = FAULT
Active = FAULT
Active = FAULT
Description
Maximum load 10 mA,
reference potential GND
0 – +10V (R
> 200k ohms)
i
0/4 – 20 mA (R
= 200 ohms)
B
Selectable with microswitch S2
0V
Maximum load 50 mA,
reference potential GND
Selectable through microswitch
LOGIC –/+
0 – +30V (R
> 12k ohms)
i
0 – +30 (R
> 12k ohms)
i
0 – +30V (R
> 12k ohms)
i
0 – +10V (R
> 200k ohms))
i
0/4 – 20 mA (R
= 200 ohms)
B
Selectable through
microswitch S3
0V
Transistor, max. 50 mA,
terminal 20 supply voltage
0 – +30V (R
= 12k ohms)
i
0 – +30V (R
= 12k ohms)
i
0 – +30V (R
= 12k ohms)
i
0 – +10V, max. 10 mA
Supply voltage for digital
output DO– max. 48 Vdc, max.
50 mA
Modbus RTU
Modbus RTU
Maximum switching load:
250 Vac/2A or 250 Vdc/0.4A
Maximum switching load:
250 Vac/2A or 250 Vdc/0.4A
Maximum switching load:
250 Vac/2A or 250 Vdc/0.4A
Maximum switching load:
250 Vac/2A or 250 Vdc/0.4A
Maximum switching load:
250 Vac/2A or 250 Vdc/0.4A
9