Evacuation; Background Music - Siemens FIREFINDER-XLS Installation, Operation And Maintenance Manual

Hide thumbs Also See for FIREFINDER-XLS:
Table of Contents

Advertisement

FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Evacuation (EVAC)
5-10
GLOBAL VOICE
The Evacuation operation consists of the following functions which are described
below: All Evacuation and Select Evacuation.
All Evacuation
All Evacuation sends, with a single switch press, the evacuation tone or message
(predetermined in the system design) to all speaker groups in the local PMI/PMI-2/
PMI-3 only. Selecting All Evacuation overrides All Alert, All Convenience Page and All

Background Music.

Global All Evacuation sends the evacuation tone or message to all speaker groups
across all PMI/PMI-2/PMI-3 nodes in the system.
To select All Evacuation, follow the steps listed below.
1.
Depress the All Evacuation switch.
2.
The All Evacuation, Display Evacuation and all Speaker Group switch LEDs
turn on steady red.
3.
All speaker groups sound the evacuation tone or message.
4.
To end All Evacuation, depress the All Evacuation switch again.
5.
The evacuation signal turns off (assuming no automatic alarms exist).
6.
The All Evacuation, Display Evacuation and all Speaker Group switch LEDs
turn off.
Select Evacuation
Select Evacuation sends the evacuation tone or message (predetermined in the
system design) to selected speaker groups in the system. The user can select local or
remote speaker groups—the selected group determines the scope. Choosing Select
Evacuation overrides Select Alert, Select Convenience Page and Select Background
Music.
To select Select Evacuation, follow the steps listed below.
1.
Depress the Select Evacuation switch, the LED turns on steady red.
2.
Depress the individual Speaker Group switches.
3.
The selected Speaker Group and the Display Evacuation switch LEDs turn
on steady red.
4.
If no Speaker Group switches are pressed for 120 seconds, the system
automatically returns to normal.
5.
The selected speaker groups sound the evacuation tone or message.
6.
To end Select Evacuation, first depress the selected Speaker Group
switches, then Select Evacuation.
7 .
The evacuation signal turns off (assuming no automatic alarms exist).
8.
The Select Evacuation, Display Evacuation and all Speaker Group switch
LEDs turn off.