Phone Page

Warden's Page

4-22
VOICE SYSTEM
Phone Page allows the user to send the emergency page message from the party
line to all speaker groups in the system. Keying the microphone on the Emergency
Page microphone will shut off the Phone Page.
To perform a Phone Page, follow the steps listed below.
1.
Depress the All Page switch (or depress Select Page and selected Speaker
Group switches).
2.
The All Page and all Speaker Group switch LEDs flash green.
3.
Depress the Phone Page switch.
4.
The Phone Page, All Page and Speaker Group switch LEDs turn on steady
green.
5.
The operator now can speak and make the page to the speaker groups.
6.
To end Phone Page, depress the Phone Page and the All Page switch again.
7 .
The Phone Page, All Page and Speaker Group switch LEDs turn off.
Warden's Page allows a remote first responder located anywhere in the building to
make a live voice page. Keying the microphone on the Emergency Page microphone
will shut off the Warden's Page.
To perform a Warden's Page, follow the steps listed below.
1.
A remote first responder lifts a Warden's Telephone Station telephone off-
hook or plugs in a Portable Telephone.
2.
The Master Telephone (FMT) handset starts to beep indicating a call-in.
3.
The LED next to the Phone Group switch flashes green.
4.
The remote first responder calling in hears a dial tone.
5.
The operator picks up the master telephone handset.
6.
The operator depresses the Phone Group switch that is calling in.
7 .
The operator and the remote first responder can now talk to each other.
8.
The first responder requests that the operator patch the phone group he is
calling in from onto the speaker group serving the area of the building that
he is calling from.
9.
The operator depresses the Select Page switch and the Speaker Group switch.
10. The operator depresses the Warden's Page switch—the LED turns on
steady green.
11.
The remote first responder can now make his live voice page to the speaker
group.
12. The operator can monitor the page from the local internal speaker.
13. The operator can interrupt, override or stop the Warden's Page.
14. To end the Warden's page, de-select all depressed switches.
15. The Warden's Page and the Speaker Group switch LEDs turn off.
16. The first responder that called in can hang up or unplug his remote telephone.
17 .
The Phone Group switch LED turns off.