FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
5-8
GLOBAL VOICE
Page to Evacuation
Page to Evacuation sends the emergency page message, with a single switch press,
from the Live Voice Module (LVM) to all speaker groups in the local PMI/PMI-2/PMI-3
only currently receiving an EVAC1 or EVAC2 signal.
Global Page to Evacuation sends an emergency page message from the LVM to all
speaker groups across all PMI/PMI-2/PMI-3 nodes in the system currently receiving
an EVAC signal.
To select Page to Evacuation, follow the steps listed below.
1.
The LEDs of the selected speaker groups receiving an evacuation signal are
steady red.
2.
Pick up the Live Voice Module.
3.
Depress the Page to Evacuation switch.
4.
The Page to Evacuation switch LED and the LEDs of the selected Speaker
Groups receiving an EVAC signal flash green.
5.
Depress the key on the Live Voice ModuleModule.
6.
The selected Speaker Group switch LEDs turn steady green indicating that
the speaker groups are now turned on.
7 .
Once the microphone is keyed, a preannouncement tone sounds on the
speaker groups for approximately three seconds (0-10 seconds is program-
mable in Zeus).
8.
While the preannouncement tone is sounding, the Pre-Announce Tone LED
is on steady to give the operator a visual indication of what is sounding.
9.
When the preannouncement tone ends, the Pre-Announce Tone LED turns
off and the Ready to Page LED turns on telling the operator to proceed with
the page.
10. The operator can now speak and make the page.
11.
During the page the operator can briefly (for up to five seconds) unkey and
then re-key the microphone (for example, to cough) without re-initiating the
pre-announce tone.
12. To end the page, the operator can simply unkey and replace the microphone,
the Ready to Page LED turns off.
13. The Page to Evacuation and the Speaker Group switch LEDs turn from
steady green to flashing green.
14. To cancel Page to Evacuation, the operator depresses the Page to Evacua-
tion switch; otherwise, the system will return to its previous state automati-
cally in approximately 1-2 minutes and turn off the Page to Evacuation LED.
15. The selected speaker groups resume receiving an evacuation signal.