CHAPTER 1 |
FTS Series Telephone
Stations
LPB Local Page Board
LVM Live Voice Module
PFT Series
TZC-8B Telephone Zone
Card
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
The FTS Series of Telephone Stations consists of
the FTS, FTS-P , FTS-C, FTS-CL and FTS-PCL models. Any of the models in the FTS
Series can mount into either the FB-300 flush backbox or the FB-301S surface
backbox. The backboxes are mounted on the wall of the facility in accordance with
local mounting codes in locations that provide easy access.
The LPB (Local Page Board) is used to connect the alarm
microphone, mounted in the LVM (Live Voice Module),
and the voice system internal telephone system. The
LPB converts the two analog input signals into the
system's internal digital format. Additionally the LPB
provides one analog output to connect the monitor
speaker, mounted in the LVM. This output signal is one
of the eight internal voice audio channels selectable at the voice control panel.
The microphone signal wiring between LVM and LPB is supervised. The microphone
audio input of the LPB is not transformer isolated (each LVM microphone output is
transformer isolated). The audio input from the telephone riser is transformer isolated.
Each of the three audio channels can be configured independently via the Zeus tool.
Each audio channel can be controlled automatically via system
logic, dependent on its individual configuration or manually by
using the voice control panel.
The LVM Live Voice Module provides first responders with a
means of sending live voice messages to specified audio
zones. The LVM has a push-to-talk switch on the microphone,
as well as a retractable coiled cord. Both the push-to talk
switch and the microphone are supervised. The LVM has a
built-in speaker to preview active tones and messages.
The PFT Series Telephones include models PFT and PFT-P . Both models have a jack at
the end of the phone that plugs into either an FJ-303(SS) or FJ-304(SS) plate. Model
PFT-P has a "push-to-talk" button.
The TZC-8B Telephone Zone Card provides a way for emergency response
personnel located throughout a building to speak with one another during
emergency situations. The card is located in any FireFinder-XLS enclosure
and is connected to jacks or FTS Telephone Stations located throughout the
building. Portable phones (Models PFT and PFT-P) that plug into these
jacks or FTS Telephone Stations (Model FTS) can communicate to the
FMT Master Telephone located at the main enclosure or to telephones
connected to the system.
TZC-8B
RESET
POWER
CARD FAIL
CAN FAIL
GND FAULT
ZONE 1 ACTIVE
TRBL
ZONE 2 ACTIVE
TRBL
ZONE 3 ACTIVE
TRBL
ZONE 4 ACTIVE
TRBL
ZONE 5 ACTIVE
TRBL
ZONE 6 ACTIVE
TRBL
ZONE 7 ACTIVE
TRBL
ZONE 8 ACTIVE
TRBL
TENS
ONES
CAN
1-17