FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
FCM-6 Control Module
HLIM Loop Isolator Module
LCM-8 LED Control Module The LCM-8 contains eight pairs of LEDs. Each pair contains one
MDACT Multi-Point Digital
XDACT (FCA2015-U1)
1-10
DESCRIPTION
The FCM-6 contains six sets of three pushbutton switches and
their corresponding LEDs. The ON and AUTO switches both have
one bi-color (red/green) LED while the OFF switch has one bi-
color and one yellow LED. The functions of the switches and
LEDs are programmed using the Zeus Tool (Refer to the Zeus
Quick Start Guide, P/N 315-033875). All LEDs can be pro-
grammed ON, OFF , or FLASHING.
The HLIM Loop Isolator Module isolates short circuits on
FireFinder-XLS intelligent loops. By placing devices between
HLIMs during installation, a short in the wiring within that group
is disconnected from the rest of the loop. The remainder of the
devices continue to operate. The HLIM operates in both Style 6
(Class A) and Style 4 (Class B) circuits.
bi-color (red/green) and one yellow LED. The functions of the
LEDs are programmed using the Zeus Tool (Refer to the Zeus
Quick Start Guide, P/N 315-033875). All LEDs can be pro-
grammed ON, OFF , or FLASHING. These LEDs are used for
system status annunciation.
The MDACT is a multipoint serial dialer for use in FireFinder-XLS Alarm Communica-
tor systems where point identification of alarm, supervisory, status or trouble
indication is required at central stations.
The XDACT (FCA2015-U1) enables remote transmission of alarms and events via the
public telephone system. The module is installed next to the PMI as per the XDACT-
ASSY Installation Instructions, Document ID A6V10807278, and is controlled by the
PMI. When replacing an MDACT with a FCA2015-U1, the Zeus configuration will need
to be updated accordingly. Features include temporarily storing alarm messages,
supervision of two independent circuits, and setting of the alarm message priority.