Advertisement

FIREFINDER-XLS CONTROL PANEL
PMI Operation Manual
P/N 315-033874-4
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
SUPERVISORY
SECURITY
ALARM
POWER
10:32:05 04/15/01
ON
SYSTEM STATUS: NORMAL
FireFinder-XLS
AUDIBLES
Siemens - Fire Safety
SILENCED
PARTIAL SYSTEM
DISABLED
Siemens Building Technologies
TROUBLE
....
More
Info
+
_
?
Fire Safety

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FIREFINDER-XLS

  • Page 1 FIREFINDER-XLS CONTROL PANEL PMI Operation Manual SUPERVISORY SECURITY ALARM TROUBLE ..POWER 10:32:05 04/15/01 SYSTEM STATUS: NORMAL FireFinder-XLS More AUDIBLES Info Siemens - Fire Safety SILENCED PARTIAL SYSTEM DISABLED Siemens Building Technologies Fire Safety P/N 315-033874-4 Technical Manuals Online! - http://www.tech-man.com...
  • Page 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 3: Table Of Contents

    PMI OPERATION MANUAL Contents INTRODUCTION ________________________________________________________________________ 1-1 Interface Overview USING THE MENU ______________________________________________________________________ 1-2 Tree Structure Physical View Geographic View Changing Views NORMAL MODE _______________________________________________________________________ 1-6 Menu ALERT MODE __________________________________________________________________________ 1-6 Alarm Supervisory Security 1-10 Trouble 1-10 24 Hour Trouble Resound 1-10 Reset Procedures 1-11...
  • Page 4 PMI OPERATION MANUAL Walktest 3-16 Suggested Procedure 3-16 Initiating The Walktest 3-17 Walktesting Groups 3-18 Duration And Termination 3-18 Event Annunciation 3-19 Walktest Ending Sequence 3-20 Voice Activations 3-20 Walktest Event Log 3-21 Walktest Reports 3-21 FUNCTION KEYS _______________________________________________________________________ 4-1 LOGOUT _______________________________________________________________________________ 4-1 DIAGNOSTICS _________________________________________________________________________ 4-2 LAMP TEST ____________________________________________________________________________ 4-2...
  • Page 5: Introduction

    SECURITY ALARM TROUBLE INTRODUCTION The PMI is the primary  user interface for the .. FireFinder-XLS system. When the PMI is installed, the display, POWER  Alarm(s) # Security(s) # Trouble(s) # Super(s) # LEDs and control keys/ Device custom message...
  • Page 6: Using The Menu

    USING THE MENU The menu gives you wide control of the FireFinder-XLS System. You may use the menu no matter what mode the system is in. The Main Menu items and the subitems of the Alert, Report and Maintenance ..
  • Page 7 CHAPTER 1 | PMI OPERATION MANUAL Alert Menu ALERT MENU Event Use More Info/+ to get: Details Devices Acknowledge Silence Unsilence Audibles Audibles Reset System REPORT MENU Use + or – Report Menu to choose level: Node APPLY Node Settings Module Module SubModule...
  • Page 8: Physical View

    | CHAPTER 1 PMI OPERATION MANUAL Maintenance Menu MAINT MENU Use + or – Geographical to choose level: View Node Module Physical Device GoTo Location View Energized (Disarm Only) De-Energized (Disarm Only) Devices Smoke/Photo Switch 1 Switch 2 Thermal Inputs Neural APPLY Disarm...
  • Page 9: Geographic View

    CHAPTER 1 | PMI OPERATION MANUAL Tree Structure In most menus, the PMI uses a tree structure to display the elements of the system. Subordinate items connected to a device are children of that device; the device connected just above the device is its parent. This tree structure closely resembles the physical arrangement of elements used in the Zeus programming tool.
  • Page 10: Normal Mode

    | CHAPTER 1 PMI OPERATION MANUAL NORMAL MODE Normal mode is the absence of any alarm, supervisory, trouble, or security conditions. The screen displays SYSTEM STATUS: NORMAL with the time and date. If a custom message has been programmed using the Zeus tool (refer to Zeus Quick Start Guide, P/N 315-033875), the node custom message also displays in this mode.
  • Page 11: Alarm

    CHAPTER 1 | PMI OPERATION MANUAL Once all events are acknowledged and audibles silenced, a Reset System soft key becomes available in the lower right side of the display. If notification appliances were active, two additional soft keys become available at the bottom of the screen. These allow the operator to silence or unsilence the notification appliances (audibles).
  • Page 12 | CHAPTER 1 PMI OPERATION MANUAL In addition, the System responds to alarms with other output functions (as pro- grammed in the Zeus tool) such as other audible signals. An Acknowledge Alarms soft key displays in the bottom left corner of the screen. Press this key to acknowledge each alarm and to silence the local audible.
  • Page 13 CHAPTER 1 | PMI OPERATION MANUAL First Floor Reception Area AREA FIRE EQUIP: ALARM LOCATION: 1st Floor Reception Area - Lobby entrance AREA CONTAINS: # Devices in ALARM: 3 ALARM TYPES: Smoke, Heat, Flow Contact: John Sample Phone #: 973.555.1234 DETAILS DEVICES BACK...
  • Page 14: Security

    | CHAPTER 1 PMI OPERATION MANUAL Security When a security is detected, the yellow Security LED blinks, the System’s internal audible pulses, and the event(s) display on the screen with a blinking exclamation mark (!). This event listing displays the Event Custom Message, the Time of the event occurrence and the Security Event Category (i.e., Door, Monitor Point, etc.).
  • Page 15: Reset Procedures

    CHAPTER 1 | PMI OPERATION MANUAL Reset Procedures There are two types of reset procedures that can be performed on the FireFinder- XLS System: Hard Reset and Soft Reset. Hard Reset Other terms for Hard Reset are Power-up, Initialization, and Cold Reset. Applying power to the system performs a Hard Reset.
  • Page 16 | CHAPTER 1 PMI OPERATION MANUAL 1-12 BASIC OPERATION Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 17: Report Mode

    REPORT MODE Report Mode is used to obtain information and create reports about the system, modules, submodules and devices. Report Options There are four options that can be selected in the Report Mode: Configuration, Status, Queue and History. Report displays are not dynamic. The information on the PMI screen is displayed at the moment the report was requested.
  • Page 18: Queue Report

    | CHAPTER 2 PMI OPERATION MANUAL The Status reports list the following information: y t i y t i i t c c t i y t i v i t y t i v i t y t i y t i v i t y t i...
  • Page 19 Report soft key. Press the More Info button on the PMI to navigate to the desired loop or specific device. When More Info is pressed once it displays the FireFinder-XLS node. • Press the More Info/+ button again to display a list of FireFinder-XLS modules;...
  • Page 20 | CHAPTER 2 PMI OPERATION MANUAL Menu:Report:Configuration PHY:FireFinder@1 Cust Msg Database Entity Type Usage Category Category text information Appl Rev Base Rev HW Rev FPGA Rev Cancel Figure 2-1 Configuration Report Selections To access, view and print any of the Configuration Reports, follow the directions described below.
  • Page 21 CHAPTER 2 | PMI OPERATION MANUAL Menu:Report:Configuration:CustMsg:Settings PHY:FireFinder@1 None Module SubModule Device Node Cancel Figure 2-3 Report Settings Selections When the Settings have been completed, press the Apply soft key to display the status screen showing the settings that were made to generate the report. See Figure 2-4.
  • Page 22 | CHAPTER 2 PMI OPERATION MANUAL Menu:Report:Configuration:CustMsg:View PHY:FireFinder@1, ZIC-4A@2 Custom Message Report Address Entity Custom Message 100% FireFinder “” ZIC-4A “ZIC-4A @ address 2” 10:53 Category text information :2-1 None “OutCkt @ address 2:1” :2-2 None “OutCkt @ address 2:2” Cancel Print GoTo...
  • Page 23 CHAPTER 2 | PMI OPERATION MANUAL Menu:Report:Status:Sensitivity PHY:FireFinder@1, DLC@1 Sensitivity Report AT: FireFinder@1, DLC@1 SETTINGS: Node: None Module: None SubModule: None Device: Smoke Cancel Settings View Figure 2-7 Sensitivity Report Settings Status Screen Press the View soft key to display the list of Detector Sensitivities. As the system reads all device sensitivities for the module/loop or device it might display the message Acquiring Data.
  • Page 24 | CHAPTER 2 PMI OPERATION MANUAL Menu:Report:Queue PHY:FireFinder@1 Trouble Alarm Supv Security Cancel Figure 2-9 Menu:Report:Queue Screen “Touch” the desired option (Alarm, Supervisory, Security or Trouble) to select it and the Report Screen appears for that option. The information in the Queue Report is divided into three separate screens, so it is necessary to press the Select soft key to toggle through the screens.
  • Page 25 CHAPTER 2 | PMI OPERATION MANUAL Menu:Report:Queue:Alarm:View PHY:FireFinder@1 Alarm Queue Report Address Device In/Out 100% GROUP Building Building group cust msg :3-3 HFP11 10:53 Category text information P:3-11 HFP11 Cancel Print GoTo Select Figure 2-12 Report:Alarm Queue Screen #3 This alarm queue report can then be printed by selecting the Print option if the system has a report logging printer.
  • Page 26: History Report

    | CHAPTER 2 PMI OPERATION MANUAL Press the History soft key to display the Event Log Report screen. See Figure 2-13. Menu:Report:History PHY:FireFinder@1 Event Log Report SETTINGS: List Type: All Queues Start Time: Not Set Stop Time: Not Set Records: 24 Cancel Settings View...
  • Page 27 CHAPTER 2 | PMI OPERATION MANUAL Enter Time/Date: 14:41:01 07/11/02 CAPS Bksp < > Cancel Done Figure 2-15 Enter Time / Date Screen When the time and date are correct, press the Done soft key. Touch the box labeled “List Type” to narrow the scope of the report. Then choose one of the following report types (See Figure 2-16): •...
  • Page 28 | CHAPTER 2 PMI OPERATION MANUAL The Event Log Report screen will display the new settings. Refer to Figure 2-17 . Menu:Report:History PHY:FireFinder@1 Event Log Report SETTINGS: List Type: Alarms Start Time: 12:00:00 07/12/02 Stop Time: 24:00:00 07/12/02 Records: 24 Cancel Settings View...
  • Page 29 CHAPTER 2 | PMI OPERATION MANUAL Menu:Report:History:View PHY:FireFinder@1 Event Log Report Address Type Time/Date 100% :3:2 Alarm 13:48:10 07/12/02 :3-3 Alarm 13:48:12 07/12/02 10:53 Category text information :3:28 Alarm 13:51:15 07/12/02 Select Cancel Print GoTo Figure 2-19 Event Log Report Screen #2 Menu:Report:History:View PHY:FireFinder@1 Event Log Report...
  • Page 30 | CHAPTER 2 PMI OPERATION MANUAL 2-14 REPORT MODE Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 31: Maintenance Mode

    There are two options that can be selected in Maintenance Mode: Control and Walktest. Press the More Info button on the PMI to navigate to the desired group, loop or specific device. When More Info is pressed once, it displays the FireFinder-XLS node. In the Physical View: •...
  • Page 32: Pmi Password Levels

    | CHAPTER 3 PMI OPERATION MANUAL Enter Password: CAPS Bksp < > Cancel Done Figure 3-1 Enter Password Screen User passwords can be changed in the Zeus Programming Tool. There are five levels of passwords for PMI access, as shown in the table that follows. e l i e l i / l o...
  • Page 33 CHAPTER 3 | PMI OPERATION MANUAL Control - Time / Date Touch the Time/Date box to change the time and/or date. Use the keyboard screen to select the correct digits as the cursor moves along. The time is set according to the 24-hour clock.
  • Page 34: Using The Disarm Feature

    More Info+/- buttons, select the Control option by pressing the Control soft key and then “Touch” the box labeled Disarm. The Disarm Devices screen displays showing the location. See Figure 3-4. In this example, AT: FireFinder-XLS@1, DLC@1, HFP11@2, where: • FireFinder@1—Node 1 of the FireFinder System • DLC@1—the DLC module at address 1 •...
  • Page 35 CHAPTER 3 | PMI OPERATION MANUAL Inputs When the Inputs box is selected, the components section of the screen displays the items that can be selected. See Figure 3-6. Items that can not be selected are grayed out. (In Figure 3-6, Switch 1 and Switch 2 are grayed out.) Make a selection of the components you wish to disarm, then press the OK soft key.
  • Page 36 | CHAPTER 3 PMI OPERATION MANUAL When you return to the system tree in Control/Maintenance, partially disarmed modules/devices are graphically shown with the symbol in the far left column and fully disarmed devices are shown with the symbol in the far left column. (Refer to Figure 3-8.) Control Walktest...
  • Page 37: Using The Arm Feature

    CHAPTER 3 | PMI OPERATION MANUAL Menu:Maint:Control:Disarm PHY:FireFinder@1, DLC@1, HFP11@2 DISARM OUTPUTS AT: FireFinder@1, DLC@1, HFP11@2 COMPONENTS: Relay 1 OUTPUT: De-Energized Cancel Settings Execute Figure 3-10 Disarm Outputs Status Screen At this point, the components that were selected are not yet disarmed. Press the Execute soft key to disarm the selected components.
  • Page 38 | CHAPTER 3 PMI OPERATION MANUAL Maint:Control:Arm:Settings PHY:FireFinder@1, DLC@1, HFP11@2 Apply To Devices Inputs Outputs Components Smoke/Photo Switch 1 Switch 2 Thermal Neural Cancel Figure 3-12 Arm Inputs Settings Inputs When the Inputs box is selected, the components section of the screen displays the items that can be chosen.
  • Page 39 CHAPTER 3 | PMI OPERATION MANUAL Menu:Maint:Control:Arm:Settings PHY:FireFinder@1, DLC@1, HFP11@2 Apply To Devices Inputs Outputs Components Relay 1 Relay 2 Status LED Cancel Figure 3-14 Arm Outputs Settings At this point, the components that were selected are not yet armed. The Arm Outputs status screen returns.
  • Page 40 | CHAPTER 3 PMI OPERATION MANUAL Bypass ASD Touch the box labeled Bypass ASD and a screen displays showing the number of devices that will be bypassed. See Figure 3-16. At this point, the ASD setting has not been bypassed. Menu:Maint:Control:BypassASD PHY:FireFinder@1, DLC@3 BYPASS ASD...
  • Page 41: Change Sensitivity

    CHAPTER 3 | PMI OPERATION MANUAL Menu:Maint:Control:ChangeASD PHY:FireFinder@1, DLC@1, HFP11@2 CHANGE ASD AT: FireFinder@1, DLC@1, HFP11@2 10:53 # ASD Devices: 1 Category text information SETTINGS: FROM: Disable Office Cancel Execute Figure 3-18 Change ASD Setting Status Screen At this point, the ASD setting has not been changed. Press the Execute soft key to change the ASD setting.
  • Page 42 | CHAPTER 3 PMI OPERATION MANUAL Press the Settings soft key to display the various %/ft. options. See Figure 3-20. Menu:Maint:Control:ChangeSensitivity:Settings PHY:FireFinder@1, DLC@1, HFP11@2 2.45% / Foot 2.59% / Foot 2.72% / Foot 2.86% / Foot 3.00% / Foot 3.13% / Foot 3.27% / Foot Cancel Figure 3-20...
  • Page 43 CHAPTER 3 | PMI OPERATION MANUAL Use the Zeus tool to extract data for future reference before erasing the system’s history, since once the history is erased it cannot be restored. Menu:Maint:Control: Clear History PHY:FireFinder@1 Clear History SETTINGS: # Records: 712 Cancel Execute Figure 3-22...
  • Page 44: Activate/Deactivate

    Device level only and is not available in Geographic View. The Activate/Deactive Devices screen displays showing the location. See Figure 3-25. In this example, AT: FireFinder-XLS@1, DLC@1, HFP11@2, where: • FireFinder@1—Node 1 of the FireFinder System •...
  • Page 45 Components section of the screen. In this example, it is Smoke/Photo. Press the Execute soft key to activate the selected component. Menu:Maint:Control:Activate PHY: FireFinder , DLC@1, HFP11@2 ACTIVATE INPUT AT: FireFinder-XLS@1, DLC@1, HFP11@2 COMPONENT: Smoke/Photo Cancel Settings Execute Figure 3-27...
  • Page 46: Walktest

    PMI OPERATION MANUAL WALKTEST A Walktest of the FireFinder-XLS System enables a qualified technician to test the operation of a specific portion of input points on a system while allowing the remainder of the system to function normally. A Walktest can be performed by Group (Geographic view) or by DLC/SIM/HZM/CDC (Physical view).
  • Page 47: Initiating The Walktest

    CHAPTER 3 | PMI OPERATION MANUAL Initiate Walktest. Test devices in a predetermined, orderly sequence. Do not test any devices that are not in the Walktest, as this will cause an alarm in the system and cancel the Walktest. In order to reduce the possibility of a false alarm, do not perform any Walktest activations for at least 5 minutes prior to the expiration of the Walktest or the planned cancellation time.
  • Page 48: Walktesting Groups

    | CHAPTER 3 PMI OPERATION MANUAL Press the Enable soft key to begin the Walktest. The Trouble LED flashes and the Walktest Enabled screen displays (See Figure 3-30). If a printer is installed, the trouble is also printed on the report printer. The PMI Trouble Event Screen will display one trouble for each DLC placed in Walktest (ASD disabled for test) and one trouble showing the Control Panel in Walktest.
  • Page 49: Event Annunciation

    CHAPTER 3 | PMI OPERATION MANUAL Alarm(s) 0 Sup(s) 0 Security(s) 0 Trouble(s) 1 WALKTEST 3:59 First Floor Reception Area 10:53 DLC@1 In Walktest Reset Acknowledge System Troubles Figure 3-31 Walktest Time Remaining In Alert Mode Upon termination, whether manual or automatic, Alarm events are reported for all devices remaining in alarm after the walktest is terminated.
  • Page 50: Walktest Ending Sequence

    | CHAPTER 3 PMI OPERATION MANUAL When No Bells is selected, there is no audible notification of Walktest events. There is no event-type coding during the Walktest. Audible notification is the same for Alarm, Supervisory, Security and Trouble events. If the system has a report printer, Walktest events will be printed with the Walktest designation “WT”...
  • Page 51: Walktest Event Log

    CHAPTER 3 | PMI OPERATION MANUAL Walktest Event Log A maximum of 5000 Walktest events will be stored in flash memory for reporting. Walktest events are automatically stored. The storage cannot be disabled by the user. Since a full walktest inspection of a system may be performed over a period of days, weeks and/or months, the Walktest log remains in memory between individual Walktest sessions.
  • Page 52 | CHAPTER 3 PMI OPERATION MANUAL Menu:Report:Status:Walktest:Settings PHY:FireFinder@1, DLC@1 Stop Time Clear Times Start Time Cancel Figure 3-34 Walktest Report Settings Screen After selecting the desired settings for the report, press the View soft key. The Walktest Report status screen displays, similar to the one shown in Figure 3-35. Menu:Report:Status:Walktest:View PHY:FireFinder@1, DLC@1 Walktest Report...
  • Page 53 CHAPTER 3 | PMI OPERATION MANUAL Press the Select soft key to toggle the screen to the Custom Messages for the devices that have been walktested. Refer to Figure 3-36. Menu:Report:Status:Walktest:View PHY:FireFinder@1, DLC@1 Walktest Report Address Type Custom Message 100% :1-5 Alarm 1st Flr Lobby 5...
  • Page 54 | CHAPTER 3 PMI OPERATION MANUAL 3-24 MAINTENANCE MODE Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 55: Function Keys

    FUNCTION KEYS If Functions keys have been programmed in the Zeus tool, they can be accessed in the Menu mode by pressing the Function soft key. The Function Key status screen appears with a listing of all the functions. See Figure 4-1. To perform a desired function, highlight the function using the up and down arrow keys and then press the Execute soft key.
  • Page 56: Diagnostics

    Figure 4-2 PMI Menu Screen - Logout DIAGNOSTICS Diagnostics displays a series of statistics typically used by Siemens Building Technologies, Inc. to evaluate the operation of the system. LAMP TEST Press the menu button to display the PMI Menu Screen. Next, press the Lamp Test soft key at the bottom of the screen.
  • Page 57 INDEX | PMI OPERATION MANUAL Index Custom Message report 2-1, 2-4 Acknowledge 1-6 Acknowledge Security 1-10 Database report 2-1 Acknowledge Supervisory 1-9 Deactivate 3-14 to 3-15 Acknowledge Trouble 1-10 Details 1-8 Activate / Deactivate 3-14 to 3-15 Diagnostics 4-2 Alarm 1-7 to 1-9 Disable History 3-13 Alternate Language 1-2, 1-6, 4-2 Disarm...
  • Page 58 | INDEX PMI OPERATION MANUAL History 2-1, 2-3, 2-9 to 2-13 Alarm 2-3 initialization. See hard reset All Non-Events 2-3 All Queues 2-3 Security 2-3 Supervisory 2-3 Lamp Test 4-2 Trouble 2-3 LEDs 1-1, 1-2 Queue 2-1, 2-2, 2-7 to 2-13 logout 4-1 to 4-2 Alarm 2-2 Security 2-2...
  • Page 59 INDEX | PMI OPERATION MANUAL Temperature report 2-2 Threshold report 2-2 Time / Date 3-3 touch screen 1-1, 1-2 tree structure 1-5 Alert Menu 1-3 Main Menu 1-2 Maintenance Menu 1-4 Report Menu 1-3 Trouble 1-10 to 1-11 24 Hour Trouble Resound 1-10 Usage report 2-1 View 2-5, 2-7 , 2-12 views...
  • Page 60 | INDEX PMI OPERATION MANUAL Index - 4 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 61 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 62 Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview Boulevard Florham Park, New Jersey 07932 Brampton, Ontario L6T 5E4 CN Siemens Building Technologies P/N 315-033874-4 Fire Safety Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...

Table of Contents