FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
2-4
INSTALLATION
8.
Install Field Wiring.
Dress the field wiring that will be going to the CC-5. Strip the insulation
from the wiring, but do not connect the wires to the screw terminals.
9.
Check Field Wiring.
Initiating Devices–Install all initiating device bases and end-of-line devices
where applicable. Install all initiating devices. Refer to the specific installa-
tion instructions provided with each device. Connect the DPU to initiating
devices and test FireFinder-XLS loops. The DPU checks that all of the
devices are communicating and also checks for ground faults and short
circuits. Refer to the DPU User's Manual, P/N 315-033260, for further
information.
Notification Appliances–Install all notification appliances (bells, strobes, etc.)
Refer to the specific installation instructions provided with each device.
10. If the PSC-12 and CC-5/CC-2 were installed on the optional CAB-MP outside
of the enclosure, mount the complete assembly in the CAB row.
11.
Connect Field Wiring to CC-5/CC-2 screw terminals, as appropriate.
12. Install card guides in CC-5/CC-2.
13. Install the required modules. Refer to the Installation Instruction Index,
P/N 315-034242 for a list of all compatilbe FireFinder-XLS system modules.
Do not place any modules behind the LVM and the FMT, specifically the PSC-12,
PSX-12, CC-5, CC-2 and ZAM-180.
14. On the PSC-12, set the circuit breaker for the battery to the OFF position.
Verify that the AC dedicated circuit breaker is turned off at the mains.
15. Connect the AC mains and battery wiring to the PTB.
16. Connect the PTB output to the PSC-12.
17 .
Turn on the dedicated circuit breaker.
18. Turn on the PSC-12 circuit breaker for the battery.
19. The System will initialize in default mode.
20. Using the Zeus programming tool, transfer the site-specific program to the
FireFinder-XLS system. Refer to the Zeus Quick Start Manual, P/N 315-
033875, for further information. Upon completion, the system will automati-
cally initialize. FireFinder-XLS will interrogate the system and verify that the
system agrees with the Zeus configuration.
21. Any problem found will be reported in the PMI/PMI-2/PMI-3. Identify all
discrepancies and correct them until the system reports SYSTEM STATUS:
NORMAL.