A Initialization Parameters; A1 Initialization Set-Up - YASKAWA VS-616PS5 Series Programming Manual

Brushless motor drive
Hide thumbs Also See for VS-616PS5 Series:
Table of Contents

Advertisement

Main Menu:Initialize <ENTER>
A
Initialization Parameters
A1
Initialization Set-up
A1-01 Parameter Access Level
This parameter allows the "masking" of parameters according to user level. See the
following table:
Setting
0
2
3
4
A1-03 Operator Status
Use this parameter to reset the inverter to its factory default settings. Initialize the
inverter after changing the control PCB, or after selecting inverter capacity (O2-04).
A1-04 Password Entry
This parameter allows password entry to view masked parameters.
VS-616PS5 Programming Manual
Operation Only
Quick Start Level (factory default) - For maintenance-level programming.
Basic Level - For basic programming in most applications.
Advanced Level - For advanced programming in special applications.
Setting
0
No Initialization (factory default).
2220
2-Wire Initialization - terminal 1 becomes FWD run command and
terminal 2 becomes REV run command. All other parameters are
reset to their original factory default settings.
3330
3-Wire Initialization - terminal 1 becomes run command, terminal 2
becomes stop command and terminal 3 becomes FWD/REV run
selection. All other parameters are reset to their original factory
default settings.
Section A: Initialization Parameters
Description
Description

A1 Initialization Set-up

Q
Q
Q