Technical data
4.4 Interfaces and performance features
If used as an output
Rated load voltage, permissible range
Galvanic isolation
Current load, max.
Residual current, max.
Output delay, typ./max. (hardware)
Cam output, resolution
Cam output, reproducibility
Switching frequency of the outputs, max.
Protection
1)
2)
3)
Fail-safe digital I/Os
Table 4- 13
Number of inputs
Input voltage
Electrical isolation
Current consumption typical at 1 signal level
Input delay, typical (hardware)
Protection
1)
2)
66
0 → 1 signal
1 → 0 signal
With resistive load
With inductive load
With lamp load (max. 5 W)
Data for: V
= 24 V; load 48 Ω; high ("1") = 90% V
cc
The digital inputs are protected against polarity reversal up to -30 V
The information was not available at the time of going to press. For the latest information, go to
http://support.automation.siemens.com/WW/view/de/27585482.
Technical data for fail-safe digital inputs (F-DI)
Rated value
For signal "1"
For signal "0"
1)
2)
0 → 1 signal
1 → 0 signal
The digital inputs are protected against polarity reversal up to -30 V
Reference potential for DI 16, DI 18, DI 20 and DO 16 is terminal M1 (X120, X130)
24 VDC, 20.4 ... 28.8 V
No
500 mA per output
2 mA
1)
150 μs / 400 μs
75 μs / 100 μs
Typ. 125 µs
3)
100 Hz
0.5 Hz
10 Hz
Short circuit, ground fault and overload proof
Automatic restart after overload tripping
; low ("0") = 10% V
out
3 F-DI (or as 6 DI)
24 VDC
15 ... 30 V
-3 ... +5 V
Yes (via optocoupler)
6 mA at 24 V
50 μs
150 μs
Short circuit, ground fault and overload proof
out