Interfaces
3.5 Digital I/Os / temperature sensor / analog input
The maximum length of the temperature sensor cable is 300 m. The cables must be
shielded. For cable lengths >100 m, cables with a cross-section of ≥1 mm² must be used.
Risk of electric shock!
Only temperature sensors that meet the electrical separation specifications contained in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp". If safe electrical
separation cannot be guaranteed (for linear motors or third-party motors, for example), a
Sensor Module External (SME120 or SME125) or Terminal Module TM120 must be used.
If these instructions are not observed, there is a risk of electric shock!
X121
Table 3- 15
Representation
1)
NOTICE
An open input is interpreted as "low".
The use of the digital inputs (DI 0 ... DI 3) requires terminal M2 be connected. This is
achieved by:
• Also routing the ground reference of the digital inputs, or
• A jumper to terminal M. This removes the electrical isolation for these digital inputs.
44
DANGER
Interface assignment X121
Pin
Designation
1
DI 0
2
DI 1
3
DI 2
4
DI 3
5
M2
6
M
7
DI/DO 8
8
DI/DO 9
9
M
10
DI/DO 10
11
DI/DO 11
12
M
Reference potential for the digital I/Os and analog input
Information
Isolated digital input 0
Isolated digital input 1
Isolated digital input 2
Isolated digital input 3
Ground reference for DI 0 - DI 3
Ground reference of the electronics
High-speed digital I/O 8,
not isolated
High-speed digital I/O 9,
not isolated
Ground reference of the electronics
High-speed digital I/O 10,
not isolated
High-speed digital I/O 11,
not isolated
Ground reference of the electronics
1)
1)
1)
SIMOTION D410-2
Manual, 02/2012