Lbs System; Cabinet Installation; External Protective Device; Power Cable - Emerson Liebert APM 15-90kVA Manual

50/60hz
Table of Contents

Advertisement

4.3

LBS System

4.3.1

Cabinet Installation

A dual bus system consists of two independent UPS systems, each containing one or more parallel
UPS modules, as shown in Figure 30. The dual bus system has high reliability and is suitable for
loads with multiple input terminals. For a single-input load, an optional static transfer switch can be
fitted to achieve the transfer between the two outputs of the dual bus system.

Figure 30 Typical dual bus system (with STS and LBS)

Main Input
UPS1A
The dual bus system uses the LBS to keep the output of the two independent UPS systems (or parallel
systems) in synchronization. One system is designated as the master, the other is designated as the
slave. The operation modes of the parallel system comprise master and/or slave operation in normal
or bypass mode.
Place the UPS modules side by side and interconnect the UPS modules according to the following
instructions.
4.3.2

External Protective Device

Refer to 3.2 - External Protective Devices.
4.3.3

Power Cable

The power cable wiring is similar to that of the UPS module. Refer to 3.1 - Power Cabling.
The bypass and rectifier input supplies must use the same neutral line input terminal. If the input
has a current leakage protective device, the current leakage protective device must be fitted upstream
of the neutral line input terminal.
4.3.4

Control Cable

For Liebert APM-to-Liebert APM dual bus system, connect the optional LBS cables between the two
UPS systems as shown in Figures 31 to 33. The J3 and J4 ports are provided on the front panel of
the bypass module, as shown in Figures 28.
NOTE
Use the shortest LBS cable that will be functional for the application and do not coil excess
cable. Separate the LBS cable from the power cables to prevent electrical inteferences.
®
Liebert
APM
Bypass
Main Input
UPS1B
Parallel
Control
Cable
Parallel System and LBS System Installation
Main Input
LBS
STS
To Load
44
Bypass
Main Input
UPS2B
UPS2A
Parallel
Control
Cable

Advertisement

Table of Contents
loading