5 SETTINGS
PATH: SETTINGS
INPUTS/OUTPUTS
VIRTUAL INPUT
1
MESSAGE
MESSAGE
MESSAGE
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the
menu) and communications protocols. All virtual input operands are defaulted to "Off" (logic 0) unless the appropri-
MANDS
ate input signal is received.
If the
VIRTUAL INPUT x FUNCTION
input. If set to "Enabled", the input operates as shown on the logic diagram and generates output FlexLogic™ operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If
sits from off to on, the output operand will be set to on for only one evaluation of the FlexLogic™ equations and then return
to off. If set to "Latched", the virtual input sets the state of the output operand to the same state as the most recent received
input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic™
equations. If the operand is to be used anywhere other than internally in a FlexLogic™ equation, it will
NOTE
likely have to be lengthened in time. A FlexLogic™ timer with a delayed reset can perform this function.
VIRTUAL INPUT 1
FUNCTION:
Disabled=0
Enabled=1
"Virtual Input 1 to ON = 1"
"Virtual Input 1 to OFF = 0"
VIRTUAL INPUT 1
TYPE:
Latched
Self - Reset
GE Multilin

VIRTUAL INPUTS

VIRTUAL INPUT 1(64)
VIRTUAL INPUT
FUNCTION: Disabled
VIRTUAL INPUT
Virt Ip 1
VIRTUAL INPUT
TYPE: Latched
VIRTUAL INPUT
EVENTS: Disabled
is to "Disabled", the input will be forced to off (logic 0) regardless of any attempt to alter the
VIRTUAL INPUT x TYPE
AND
AND
AND
Figure 5–41: VIRTUAL INPUTS SCHEME LOGIC
C30 Controller System
Range: Disabled, Enabled
1
Range: Up to 12 alphanumeric characters
1 ID:
Range: Self-Reset, Latched
1
Range: Disabled, Enabled
1
is "Self-Reset", when the input signal tran-
S
Latch
R
5.7 INPUTS/OUTPUTS
5.7.2 VIRTUAL INPUTS
COM-
VIRTUAL INPUT 1 ID:
(Flexlogic Operand)
OR
Virt Ip 1
827080A2.CDR
5-99