Process Bus Modules - GE C30 Instruction Manual

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

3 HARDWARE
The C30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin
HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units,
known as Bricks. The HardFiber system has been designed to integrate seamlessly with the existing UR-series applica-
tions, including protection functions, FlexLogic™, metering, and communications.
The IEC 61850 process bus system offers the following benefits.
Drastically reduces labor associated with design, installation, and testing of protection and control applications using
the C30 by reducing the number of individual copper terminations.
Integrates seamlessly with existing C30 applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules.
Communicates using open standard IEC 61850 messaging.
For additional details on the HardFiber system, refer to GE publication GEK-113500: HardFiber System Instruction Manual.
Every digital input/output module has 24 terminal connections. They are arranged as three terminals per row, with eight
rows in total. A given row of three terminals may be used for the outputs of one relay. For example, for form-C relay outputs,
the terminals connect to the normally open (NO), normally closed (NC), and common contacts of the relay. For a form-A
output, there are options of using current or voltage detection for feature supervision, depending on the module ordered.
The terminal configuration for contact inputs is different for the two applications.
The digital inputs are grouped with a common return. The C30 has two versions of grouping: four inputs per common return
and two inputs per common return. When a digital input/output module is ordered, four inputs per common is used. The four
inputs per common allows for high-density inputs in combination with outputs, with a compromise of four inputs sharing one
common. If the inputs must be isolated per row, then two inputs per common return should be selected (4D module).
The tables and diagrams on the following pages illustrate the module types (6A, etc.) and contact arrangements that may
be ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is open,
and the DC current through the output contact when it is closed. Each of the monitors contains a level detector whose out-
put is set to logic "On = 1" when the current in the circuit is above the threshold setting. The voltage monitor is set to "On =
1" when the current is above about 1 to 2.5 mA, and the current monitor is set to "On = 1" when the current exceeds about
80 to 100 mA. The voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be
used to seal-in the output contact until an external contact has interrupted current flow.
Block diagrams are shown below for form-A and form-A / solid-state relay outputs with optional voltage monitor, optional
current monitor, and with no monitoring
GE Multilin
C30 Controller System
3.2 WIRING

3.2.4 PROCESS BUS MODULES

3.2.5 CONTACT INPUTS AND OUTPUTS
3
3-13