5.2 PRODUCT SETUP
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
BINARY INPUT / MSP
POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
ANALOG INPUT / MME
POINTS
5
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP /
IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point
NOTE
are ignored.
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the C30 is restarted.
NOTE
5-16
COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off
COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off
C30 Controller System
DNP / IEC104 POINT LISTS
Range: FlexLogic™ operand
0
Range: FlexLogic™ operand
1
Range: FlexLogic™ operand
255
DNP / IEC104 POINT LISTS
Range: any FlexAnalog parameter
0
Range: any FlexAnalog parameter
1
Range: any FlexAnalog parameter
255
5 SETTINGS
BINARY INPUT / MSP POINTS
ANALOG INPUT / MME POINTS