Dielectric Strength - GE C30 Instruction Manual

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

3 HARDWARE
The dielectric strength of the UR-series module hardware is shown in the following table:
Table 3–1: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE
MODULE FUNCTION
TYPE
1
Power supply
1
Power supply
1
Power supply
2
Reserved
3
Reserved
4
Reserved
5
Analog inputs/outputs
6
Digital inputs/outputs
G.703
7
RS422
9
CPU
Filter networks and transient protection clamps are used in the hardware to prevent damage caused by high peak voltage
transients, radio frequency interference (RFI), and electromagnetic interference (EMI). These protective components can
be damaged by application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the specified one min-
ute.
GE Multilin
TERMINALS
FROM
High (+); Low (+); (–)
48 V DC (+) and (–)
Relay terminals
N/A
N/A
N/A
All except 8b
All
All except 2b, 3a, 7b, 8a
All except 6a, 7b, 8a
All
C30 Controller System

3.2.2 DIELECTRIC STRENGTH

DIELECTRIC STRENGTH
(AC)
TO
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
N/A
N/A
N/A
N/A
N/A
N/A
Chassis
< 50 V DC
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
Chassis
< 50 V DC
Chassis
2000 V AC for 1 minute
3.2 WIRING
3
3-11

Advertisement

Table of Contents
loading

Table of Contents