GE C30 Instruction Manual page 171

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5 SETTINGS
Table 5–4: DIRECT INPUT AND OUTPUT DATA RATES
MODULE
CHANNEL
74
Channel 1
Channel 2
7L
Channel 1
Channel 2
7M
Channel 1
Channel 2
7P
Channel 1
Channel 2
7T
Channel 1
7W
Channel 1
Channel 2
7V
Channel 1
Channel 2
2A
Channel 1
2B
Channel 1
Channel 2
2G
Channel 1
2H
Channel 1
76
Channel 1
77
Channel 1
Channel 2
75
Channel 1
Channel 2
7E
Channel 1
Channel 2
7F
Channel 1
Channel 2
7G
Channel 1
Channel 2
7Q
Channel 1
Channel 2
7R
Channel 1
7S
Channel 1
Channel 2
The G.703 modules are fixed at 64 kbps. The
NOTE
The
DIRECT I/O CHANNEL CROSSOVER
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the
Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged.
GE Multilin
SUPPORTED DATA RATES
64 kbps
64 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps
64 kbps
64 kbps
128 kbps
128 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
DIRECT I/O DATA RATE
setting applies to C30s with dual-channel communication cards and allows crossing
C30 Controller System
5.2 PRODUCT SETUP
setting is not applicable to these modules.
5
5-51

Advertisement

Table of Contents
loading

Table of Contents