5 SETTINGS
The measured value settings for each of the 32 analog values are shown below.
PATH: SETTINGS
PRODUCT...
GGIO4 ANALOG
1
MEASURED VALUE
MESSAGE
MESSAGE
MESSAGE
These settings are configured as follows.
ANALOG IN 1 VALUE: This setting selects the FlexAnalog value to drive the instantaneous value of each GGIO4 ana-
log status value (GGIO4.MX.AnIn1.instMag.f).
ANALOG IN 1 DB: This setting specifies the deadband for each analog value. Refer to IEC 61850-7-1 and 61850-7-3
for details. The deadband is used to determine when to update the deadbanded magnitude from the instantaneous
magnitude. The deadband is a percentage of the difference between the maximum and minimum values.
ANALOG IN 1 MIN: This setting specifies the minimum value for each analog value. Refer to IEC 61850-7-1 and
61850-7-3 for details. This minimum value is used to determine the deadband. The deadband is used in the determina-
tion of the deadbanded magnitude from the instantaneous magnitude.
ANALOG IN 1 MAX: This setting defines the maximum value for each analog value. Refer to IEC 61850-7-1 and
61850-7-3 for details. This maximum value is used to determine the deadband. The deadband is used in the determi-
nation of the deadbanded magnitude from the instantaneous magnitude.
Note that the
ANALOG IN 1 MIN
numbers. Because of the large range of these settings, not all values can be stored. Some values may be rounded
NOTE
to the closest possible floating point number.
The report control configuration settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
REPORT 1
CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Changes to the report configuration will not take effect until the C30 is restarted.
Please disconnect any IEC 61850 client connection to the C30 prior to making setting changes to the report config-
uration. Disconnecting the rear Ethernet connection from the C30 will disconnect the IEC 61850 client connection.
NOTE
GE Multilin
COMMUNICATIONS
IEC 61850...
ANALOG IN
1 VALUE:
Off
ANALOG IN
1 DB:
0.000
ANALOG IN
1 MIN:
0.000
ANALOG IN
1 MAX:
0.000
and
settings are stored as IEEE 754 / IEC 60559 floating point
ANALOG IN 1 MAX
COMMUNICATIONS
IEC 61850...
REPORT 1
RptID:
REPORT 1
OptFlds:
0
REPORT 1
BufTm:
0
REPORT 1
TrgOps:
0
REPORT 1
IntgPd:
C30 Controller System
GGIO4...
GGIO4 ANALOG 1(32) MEASURED VALUE
Range: any FlexAnalog value
Range: 0.000 to 100.000 in steps of 0.001
Range: –1000000000.000 to 1000000000.000 in steps
of 0.001
Range: –1000000000.000 to 1000000000.000 in steps
of 0.001
REPORT...
REPORT 1(6) CONFIGURATION
Range: up to 66 alphanumeric characters
Range: 0 to 65535 in steps of 1
Range: 0 to 4294967295 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 4294967295 in steps of 1
0
5.2 PRODUCT SETUP
5
5-25