Sm 335 Static Parameters - Siemens SIMATIC SM 335 Manual

High-speed analog input/output module for the simatic s7-300
Hide thumbs Also See for SIMATIC SM 335:
Table of Contents

Advertisement

3.3.1

SM 335 static parameters

The static parameters can only be modified via HW Config.
Data Record 0
Data record 0 of the SM 335 contains static parameters (see Table 3-10)
Table 3-10
Byte
0
1
Diagnostics
The "Input and output diagnostics" parameter is used to specify in HW Config
which analog inputs and outputs are to trigger a diagnostic interrupt in the event of
an error.
Analog output CH3
Analog output CH2
Analog output CH1
= '1': Diagnostic interrupt enabled
= '0': Diagnostic interrupt disabled
Fig. 3-2
If the diagnostics for inputs are enabled, the SM 335 checks for common-mode
errors and measuring range violations.
When you enable diagnostics for the outputs, the SM 335 executes a short-circuit
test on the outputs.
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
6ES7 335-7HG00-8BA1
SM 335 parameters in Data Record 0
Content
Input and output diagnostics
Reserved
7 6 5 4 3 2 1 0
Analog output CH0
Meaning of the bits in the "input and output diagnostics" byte
Data Exchange with the SM 335
Default
00
H
00
H
Analog input CH0
Analog input CH1
Analog input CH2
Analog input CH3
= '1': Diagnostic interrupt enabled
= '0': Diagnostic interrupt disabled
3-17

Hide quick links: