Analog Value Representation For Analog Output Channels - Siemens SIMATIC SM 335 Manual

High-speed analog input/output module for the simatic s7-300
Hide thumbs Also See for SIMATIC SM 335:
Table of Contents

Advertisement

Data Exchange with the SM 335
3.1.4

Analog value representation for analog output channels

The table contains the analog value representation of the SM 335's output chan-
nels.
12 bits (+VZ) of the output value are converted in the 0-10 Volt range.
Bit 0, Bit 1 and Bit 2 are not converted.
11 bits + VZ of the output value are converted in the + 10 Volt range.
Bit 0, Bit 1, Bit 2 and Bit 3 are not converted.
Table 3-7
Output Value
decimal
32767
:
32512
32504
32496
:
27664
27656
27648
:
20736
:
16
8
0
–8
–16
:
–20736
:
–27648
–27656
–27648
:
–32496
–32504
–32512
:
–32768
3-10
Analog Value Representation in the Output Ranges from 0 to 10 V and + 10 V
hexa-
decimal
7FFF
Overflow
H
:
(off circuit and de-ener-
7F00
gized)
H
7EF8
Overrange
H
7EF0
H
:
6C10
H
6C08
H
6C00
Rated range
H
:
5100
H
:
10
H
8
H
0
H
FFF8
H
FFF0
H
:
AF00
H
:
9400
H
93F8
Underrange
H
93F0
H
:
8110
H
8108
H
8100
Underflow
H
:
(off circuit and de-ener-
8000
gized)
H
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
Range
0-10 V
0 V
:
0 V
11.756 V
11.753 V
:
10.006 V
10.003 V
10 V
:
7.5 V
:
5.787 mV
2.8936 mV
0 V
0 V
0 V
:
0 V
:
0 V
0 V
0 V
:
0 V
0 V
0 V
:
0 V
Output Voltage
+10 V
0 V
:
0 V
11.753 V
11.753 V
:
10.006 V
10 V
10 V
:
7.5 V
:
5.787 mV
0 V
0 V
0 V
–5.787 mV
:
–7.5 V
:
–10 V
–10 V
–10.006 V
:
–11.753 V
–11.753 V
0 V
:
0 V
6ES7 335-7HG00-8BA1