Siemens SIMATIC SM 335 Manual page 62

High-speed analog input/output module for the simatic s7-300
Hide thumbs Also See for SIMATIC SM 335:
Table of Contents

Advertisement

Data Exchange with the SM 335
Analog output value
With Comparator 1 or 2, the SM 335 outputs the specified analog values on up to 3
analog outputs (see Section 5.2).
Comparator time (DR1, Byte 10)
During the time Comparator 2 is active, the SM 335 cannot generate a hardware
interrupt for the end-of-cycle. It can therefore happen that the SM 335 does not
generate an end-of-cycle interrupt for an extended period.
You can use the comparator time to specify how long the comparator can remain
active.
If the comparator is active and the comparator time has expired, the SM 335
switches back autonomously to "Conditional Cycle" or "Free Cycle" mode.
The comparator time is specified in milliseconds (1 = 1 ms, 2 = 2 ms,
to 0 = 256 ms).
Dynamic measuring cycle control (DR1, byte 11)
The dynamic measuring cycle control byte has the following assignments in
"Comparator Mode 1":
= 0: Switch mode off
= 1: Switch mode on
"Measuring Only" mode
"Comparator" mode
Fig. 3-6
Bit 4 in the "dynamic measuring control" byte must be '1'.
3-24
7 6 5 4 3 2 1 0
= 1:
Comparator Mode
Meaning of the bits in the "dynamic measuring cycle control" byte
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
Analog input
Comparator 1
00 – Analog input CH0
01 – Analog input CH1
10 – Analog input CH2
11 – Analog input CH3
Analog input
Comparator 2
00 – Analog input CH0
01 – Analog input CH1
10 – Analog input CH2
11 – Analog input CH3
6ES7 335-7HG00-8BA1