Initializing The Sm 335'S Interval Counter Input - Siemens SIMATIC SM 335 Manual

High-speed analog input/output module for the simatic s7-300
Hide thumbs Also See for SIMATIC SM 335:
Table of Contents

Advertisement

4.4

Initializing the SM 335's interval counter input

Parameter assignments
The interval counter on the SM 335 requires no parameters. The pulse input func-
tions independently of the parameters assigned to the remaining analog channels.
The pulse input, therefore, does not have to be parameterized. The external
counter can be retrospectively parameterized with a timeout.
Monitoring time
After the monitoring time has expired, the interval duration FFFFFF
This means that a failure can be detected early (not only after 8.3 seconds).
The monitoring time is calculated as follows:
Special case: As a default, '0' equates to 8.388 seconds.
Examples:
• Byte 13 (DS1) = 1 → monitoring time = 0.032765625 seconds
• Byte 13 (DS1) = 2 → monitoring time = 0.016382812 seconds
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
6ES7 335-7HG00-8BA1
Monitoring time + 8.388
256
Interval Counter Input
· Byte 13 of DS1 [unit seconds]
is initialized.