Module Diagnostic Byte 4 (Byte 3) - Siemens SIMATIC SM 335 Manual

High-speed analog input/output module for the simatic s7-300
Hide thumbs Also See for SIMATIC SM 335:
Table of Contents

Advertisement

Data Exchange with the SM 335
3.4.6

Module diagnostic byte 4 (byte 3)

Format
Two different errors are flagged in module diagnostic byte 4
(see Figure 3-13).
7 6 5 4 3 2 1 0
Fig. 3-13
EEPROM fault
Bit 2 is set in module diagnostic byte 4 when the SM 335 detects an internal error
in the EEPROM.
ADC/DAC fault
Bit 4 is set in module diagnostic byte 4 when the SM 335 detects an analog-digital
or digital-analog conversion fault.
Such an error might occur for one of three reasons:
• No 24 V load voltage or below 15 V
• EMC problem
• Internal hardware fault
3-36
EEPROM
ADC/DAC fault
Module diagnostic byte 4
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300