Mes-
Cause
sage
534
Information message: disk is full.
535
Disk access error.
536
Disk transfer error.
537
Information message: disk is blank.
538
Simultaneous accessing of data record by job and
operator.
539
The data records in the RAM for recipe no. x con-
tained errors and have been deleted.
540
The maximum number of data records has al-
ready been created.
541 ...
Specified variable not available on PLC
550
551
An MPI/PPI connection to the PLC cannot be
established using the specified station address.
570
Variable contains errors: variable name from Pro-
Tool is used as parameter.
571
S7 system diagnosis/ALARM_S returns error if
OP logs on/off.
600
Configuration error: overflow warning at basic
setting 1
601
Configuration error: message logging at basic
setting 1
602
Configuration of remaining buffer space incor-
rect.
604
Message does not exist.
605
Process link is only configured symbolically.
606
Too many message variables configured.
607
Data type configured does not exist.
608
The process screen number does not exist.
609
Special object or operator object for message text
does not exist or is not permissible.
610
Operator object for header or footer does not exist
or is not permissible.
611
Special operator object for buffer printout does
not exist or is not permissible.
613
Data block not available or too short.
614
No entry present for log (header and footer not
present).
B-10
Remedy:
Check the physical connection.
Repeat uncompleted accessing ope-
ration.
If data records are stored in the Flash
memory they will remain valid.
Change configuration and retransfer.
Check MPI station addresses and wi-
ring.
Check configuration. Frequently oc-
curs with NC variables and when
multiplexing.
CPU operating system out of date.
Correct the remaining buffer space
and retransfer configuration.
Configure message.
Change configuration and retransfer.
g
g
Change configuration and retransfer.
g
g
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
g
, p
MATIC Hotline.
MATIC H li
Create data block of required length
on the PLC.
Configure log fully.
Equipment Manual OP7, OP17