Mes-
Cause
sage
507
Transfer of the data record was not acknowledged
by the PLC within a certain period.
509
Firmware version is different from standard FB
version.
510
Data record not present.
511
You have used a PLC job to select a recipe or a
request data record that does not exist.
512
Configured data block length is too short.
The variable transferred with the message
identifies the number of the data block.
516
SINEC L2 protocol configured but no interface
module inserted.
518
Interface module inserted and protocol configured
do not match.
520
Excessive number of saved returns has meant that
maximum nesting level has been exceeded.
521,
Screen can not be constructed or selected because
522
there is not enough memory available.
Message 522 triggers a restart with memory opti-
mization.
523
No text found.
524
Object class does not exist.
525
Illegal operand.
526
Loop-through operation is set on the OP.
527
Access to recipe data is not possible at present.
528
Recipe does not exist.
529
File does not exist.
530
Data record not present.
531
Data record can not be loaded.
532
Information message: data record memory is full.
533
Floppy connection unclear.
Equipment Manual OP7, OP17
Release 04/99
Remedy:
Checking of data records by the user
at the PLC end must be carried out
more quickly (< 10 s).
Please contact the SIMATIC Hotline.
A process link with a non-existent
data block has been configured in a
recipe or the recipe data contains er-
rors.
Change configuration and retransfer.
Change configuration and retransfer.
Change configuration and retransfer.
Go to Message Level (by pressing
ESC key if necessary).
You can optimize memory availabi-
lity by
1. Removing unused fields from the
configuration
2. Configuring the screen with fewer
fields, or splitting it into more than
one screen
3. Creating fewer recipe data re-
cords
Change mode from "Loop-through
operation" to "Normal operation".