Siemens OP7 Equipment Manual page 157

Simatic hmi. operator panel
Hide thumbs Also See for OP7:
Table of Contents

Advertisement

Mes-
Cause
sage
637
Missing configuration for an event message
638,
Actual value field for event message has only
639
been created symbolically.
640
Alarm message is not configured
641
Alarm message triggered is not configured
642,
The actual value field for alarm message has only
643
been created symbolically.
645
Internal error
PLC co-ordination area not receivable during
startup.
648
The driver number configured can not be inter-
preted.
649
Internal error
Driver number configured can not be interpreted.
650
Missing area pointer.
651
Internal error
There is not at least one data record for every re-
cipe.
652
Configuration is not compatible with S5
653
The configured user version number does not
match the version number stored on the PLC.
654
The PLC acknowledgement area has not been
configured to follow on physically from the mes-
sage area.
655
PLC acknowledgement area does not physically
follow on from the alarm messages area (–> no
startup).
656
Configured protocol is not possible.
657
Configured PLC protocol is not possible.
658
Configured PLC protocol is not possible.
659
Illegal process link in recipe, destination does not
exist.
660
Invalid destination configured for return reference
in menu.
Equipment Manual OP7, OP17
Release 04/99
Remedy:
Configure event message (–> message
g
g (
number) fully.
b ) f ll
Configure alarm message (–> mes-
g
g (
sage number).
b )
Reconfigure alarm message (–> mes-
sage number).
Press key to restart.
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
MATIC Hotline.
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
MATIC Hotline.
Configure an area pointer.
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
MATIC Hotline.
Change configuration and retransfer.
If the fault is not corrected by perfor-
ming a restart, please contact the SI-
MATIC Hotline.
Change configuration and retransfer.
Check protocol in configuration.
Use current firmware version or con-
figure different protocol.
Change configuration and retransfer.
Break key on OP; complete configu-
ration and retransfer
g
B-13