5 Installation and Wiring
5-2-2

Unit Arrangement

This section describes how to arrange the CP1E Units.
As shown in the following diagrams, Units can be arranged in one or two rows when Expansion I/O
Units or Expansion Units are used.
Arrangement in One Row
Expansion I/O Units and Expansion Units can be installed in a side-by-side arrangement.
CP1E CPU Unit
Precautions for Correct Use
Precautions for Correct Use
When connecting CP-series Expansion Units or Expansion I/O Units to a CPU Unit with AC
power, provide a space of approximately 10 mm between the CPU Unit and the first Expansion
Unit or Expansion I/O Unit.
If sufficient space cannot be provided between the CPU Unit and the first Expansion Unit or
Expansion I/O Unit, use the PLC in an ambient temperature of 0 to 50°C.
Arrangement in Two Rows
The Units can be arranged in two rows using the CP1W-CN811 I/O Connecting Cable (800 mm).
Precautions for Correct Use
Precautions for Correct Use
I/O Connecting Cable can be used in one place only in each CP1E PLC. It cannot be used in
more than one place in the same CP1E PLC.
5-6
CP-series Expansion Units and Expansion I/O Units
CP1W-CN811 I/O
Connecting Cable
CP1E CPU Unit Hardware User's Manual(W479)