DIP Switch Setting
The NT-AL001 RS-232C/RS-422A Conversion Unit has a DIP switch for setting RS-422A/485
communications conditions.
When connecting the Serial Communications Option Board, refer to the DIP switch settings shown
in the following table.
Pin
1
Not used. (Leave set to ON.)
2
Built-in terminating resistance setting
ON: Connects terminating resistance, OFF: Disconnects terminating resis-
tance
3
2/4-wire setting
2-wire: Set both pins to ON, 4-wire: Set both pins to OFF
4
5
Transmission mode setting*
Constant transmission: Set both pins to OFF.
6
Transmission performed when CS signal in RS-232C interface is at high level:
Set pin 5 to OFF and pin 6 to ON.
Transmission performed when CS signal in RS-232C interface is at low level:
Set pin 5 to ON and pin 6 to OFF.
* When connecting to a CP-series CPU Unit, turn OFF pin 5 and turn ON pin 6.

Application Example

CP1E N/NA
(S)-type CPU Unit
Built-in RS-232C Port or RS-232C
Option Board
Pin
Signal
2
SD
3
RD
4
RS
5
CS
6
+5V
7
DR*
8
ER*
9
SG
Hood
FG
* DR and ER signals are not supported by the N
Note The following cables can be used for this connection.
It is recommended that one of these cables be used to connect the RS-232C port on the Option Board
to the NT-AL001 RS-232C/RS-422 Conversion Unit.
Length
70cm
2m
CP1E CPU Unit Hardware User's Manual(W479)
Function
RS-232C/RS422A Conversion Unit
NT-AL001
RS-232C
Pin
Signal
3
RD
2
SD
4
RS
5
CS
+5V
6
7
DR
8
ER
9
SG
Hood
FG
Shield
(See note)
Model numbers
XW2Z-070T-1
XW2Z-200T-1
Remote device
RS-422
Signal
Pin
Signal
SDA
4
RDA
SDB
3
RDB
RDA
6
SDA
RDB
5
SDB
1
GRD
Remote device
Signal
RDA
RDB
SDA
SDB
FG
S(1)-type CPU Unit.
Appendices
Factory setting
ON
ON
OFF
OFF
ON
OFF
A-47