6-1-9

CPU Errors

CPU Unit Indicators
POWER
RUN
ERR/AL
INH
PRPHL
BKUP
A CPU error or fatal error may have occurred if the ERR/ALM indicator lights during operation (RUN
mode or MONITOR mode), the RUN indicator turns OFF, and operation stops.
CPU Unit Errors
A WDT (watchdog) error occurred in the CPU
Unit.
(This does not occur in normal use.)
Reference
Error flag
Error code (A400)
Error information
Note Just as when a CPU error occurs, the RUN indicator will turn OFF and the ERR/ALM indicator will
light when a fatal error occurs. Connecting the CX-Programmer, however, is possible for fatal
errors but not for CPU errors.
If the CX-Programmer cannot be connected (online), a CPU error has probably occurred.
CP1E CPU Unit Hardware User's Manual(W479)
: Not lit
: Flashing
: Lit
POWER
RUN
ERR/ALM
INH
PRPHL
BKUP
—: Irrelevant
Cause
Remedy
Cycle the power supply.
The Unit may be faulty. Consult your OMRON representative.
6 Troubleshooting