Figure 2-9. Transmitter Alarm
and Security Jumper Locations
Without LCD Display
With LCD Display
www.aotewell.com
.
Alarm
Security
Alarm
Security

Without a display installed

The failure mode alarm jumper is located on the front side of the electronics
module just inside the electronics housing cover and is labeled ALARM (See
Figure 2-9). Do not remove the transmitter cover in explosive atmospheres
when the circuit is alive. Both covers must be fully engaged to meet
explosion-proof requirements.

With a display installed

The failure mode alarm jumper is located on the LCD faceplate in the
electronics module side of the transmitter housing and is labeled ALARM
(See Figure 2-9). Do not remove the transmitter cover in explosive
atmospheres when the circuit is alive. Both covers must be fully engaged to
meet explosion proof requirements.
sales@aotewell.com
Rosemount 2088 and 2090
Low Power without LCD Display
Security
Low Power with LCD Display
Security
Industry Automation
Alarm
Alarm
2-17
+86-755-8660-6182