Rosemount 2088 and 2090
Figure 2-4. Installation
Examples
GAS
SERVICE
2-10
www.aotewell.com
Steam Flow Measurement
Place taps to the side of the line.
Mount the transmitter below the taps to ensure that impulse piping will
remain filled with condensate.
In steam service above 250 °F (121 °C), fill impulse lines with water to
prevent steam from contacting the transmitter directly and to ensure
accurate measurement start-up.
NOTE
For steam or other elevated temperature services, it is important that
temperatures at the process connection do not exceed the transmitter's
process temperature limit, which is 250 °F (121 °C).
LIQUID SERVICE
sales@aotewell.com
Industry Automation
Reference Manual
00809-0100-4690, Rev FC
June 2011
STEAM SERVICE