Figure 2-4. Installation
Examples
GAS
SERVICE
2-10
www.aotewell.com
Steam Flow Measurement
•
Place taps to the side of the line.
•
Mount the transmitter below the taps to ensure that impulse piping will
remain filled with condensate.
•
In steam service above 250 °F (121 °C), fill impulse lines with water to
prevent steam from contacting the transmitter directly and to ensure
accurate measurement start-up.
NOTE
For steam or other elevated temperature services, it is important that
temperatures at the process connection do not exceed the transmitter's
process temperature limit, which is 250 °F (121 °C).
LIQUID SERVICE
sales@aotewell.com
Industry Automation
Reference Manual
00809-0100-4690, Rev FC
June 2011
STEAM SERVICE