Emerson Rosemount 2090P Reference Manual page 67

Pressure transmitters with 4-20 ma hart and 1-5 vdc low power protocol
Hide thumbs Also See for Rosemount 2090P:
Table of Contents

Advertisement

Reference Manual
00809-0100-4690, Rev FC
June 2011
www.aotewell.com
Message
Out of memory for hotkey
configuration. Delete
unnecessary items.
Overwrite existing configuration
memory
Press OK...
Restore device value?
ROM checksum error ON
Save data from device to
configuration memory
Saving data to configuration
memory.
Sending data to device.
Sensor board not initialized ON
There are write only variables
which have not been edited.
Please edit them.
There is unsent data. Send it
before shutting off?
Too few data bytes received
Transmitter Fault
Units for <variable label> has
changed. Unit must be sent
before editing, or invalid data
will be sent.
Unsent data to online device.
SEND or LOSE data
Upgrade 475 software to access
XMTR function.
Continue with old description?
Use up/down arrows to change
contrast. Press DONE when
done.
Value out of range
<message> occurred
reading/writing <variable label>
<variable label> has an
unknown value. Unit must be
sent before editing, or invalid
data will be sent.
sales@aotewell.com
Rosemount 2088 and 2090
Description
There is no more memory available to store additional
hotkey items. Unnecessary items should be deleted to
make space available.
Requests permission to overwrite existing configuration
either by a device-to-memory transfer or by an offline
configuration. User answers using the softkeys.
Press the OK softkey. This message usually appears after
an error message from the application or as a result of
HART communications.
The edited value that was sent to a device was not
properly implemented. Restoring the device value returns
the variable to its original value.
Checksum of transmitter software has detected a fault.
Replace the electronics board.
Prompts user to press SAVE softkey to initiate a
device-to-memory transfer.
Data is being transferred from a device to configuration
memory.
Data is being transferred from configuration memory to a
device.
The sensor module electronics board is not initialized.
Replace the transmitter.
There are write-only variables which have not been set by
the user. These variables should be set or invalid values
may be sent to the device.
Press YES to send unsent data and turn the HC off. Press
NO to turn the HC off and lose the unsent data.
Command returns fewer data bytes than expected as
determined by the device description.
Device returns a command response indicating a fault
with the connected device.
The engineering units for this variable have been edited.
Send engineering units to the device before editing this
variable.
There is unsent data for a previously connected device
which must be sent or thrown away before connecting to
another device.
The communicator does not contain the most recent 2051
Device Descriptors (DDs). Select YES to communicate
using the existing DDs. Select NO to abort
communication.
Gives direction to change the contrast of the HC display.
The user-entered value is either not within the range for
the given type and size of variable or not within the
min/max specified by the device.
Either a read/write command indicates too few data bytes
received, transmitter fault, invalid response code, invalid
response command, invalid reply data field, or failed pre-
or post-read method; or a response code of any class
other than SUCCESS is returned reading a particular
variable.
A variable related to this variable has been edited. Send
related variable to the device before editing this variable.