Uponor Smatrix Base Installation And Operation Manual page 34

Hide thumbs Also See for Smatrix Base:
Table of Contents

Advertisement

UK
To connect a heating/cooling output to a sub
controller (Base PRO with interface only):
CZ
The illustration below shows components of the
heating/cooling system connected to a sub controller.
DE
DK
PUMP
EE
ES
FI
FR
PUMP
HR
HU
IT
W
!
arning
Electrical installation and service behind
LT
secured 230 V AC covers must be carried
out under the supervision of a qualified
electrician.
LV
NL
NO
PL
PT
RO
RU
SE
SK
3 4
N O T E !
This connection requires a dry contact
sensing input in the component producing
heating/cooling.
1. Ensure that the power is disconnected from both
the sub controller and the heating/cooling relay.
2. Connect the cable to/from the component
producing heating/cooling to the connector labelled
PUMP on the sub controller.
4. Go to menu Integration in the interface and select
Controller relay.
5. Select Common and enter the Settings menu that
appears.
6. Select the sub controller to which the cable is
connected to and set the output to H/C switch.
7. Go to menu Heating/cooling in the interface and
select Cooling available.
8. Enter the submenu Operating mode to the
settings menu to Heating/cooling and select H/C
Master.
9. Enter the settings menu to H/C Master in
Heating/cooling > Operating mode and select
Force cooling or Force heating to select either
cooling or heating.
10. Verify that the relay closes, when in cooling mode,
and opens, when in heating mode.
Heating/cooling output is now installed and activated.
U P O N O R S M AT R I X B A S E / B A S E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L