Event Codes - ABB SPAC 536 C User Manual

Feeder terminal
Table of Contents

Advertisement

Data
No. of AR cycles 2 initiated by AR1 0
No. of AR cycles 2 initiated by AR2 0
No. of AR cycles 2 initiated by AR3 0
Total number of AR cycles 3
No. of AR cycles 3 initiated by AR1 0
No. of AR cycles 3 initiated by AR2 0
No. of AR cycles 3 initiated by AR3 0
Total number of AR cycles 4
No. of AR cycles 4 initiated by AR1 0
No. of AR cycles 4 initiated by AR2 0
No. of AR cycles 4 initiated by AR3 0
Total number of AR cycles 5
No. of AR cycles 5 initiated by AR1 0
No. of AR cycles 5 initiated by AR2 0
No. of AR cycles 5 initiated by AR3 0
Store data into EEPROM
Load default values after EEPROM
failure
Event mask
Event mask
Event mask
Event mask
Event mask
Event mask
Activation of self-supervision
output
Internal fault code
Data communication address
Data transfer rate
Program version symbol
Type designation of the module
Reading of event register
Re-reading of event register
Reading of module status
information
Resetting of module status
information
Time reading and setting
R
= Data which can be read from the module
W = Data which can be written to the module
(e) = Data which has to be stored in EEPROM (V151) after it has been changed
The data transfer codes L, B, C and T have been
reserved for event data transfer between the
control module and the station level data com-
municator.
Channel Code
Data
direction
V25
RW
V26
RW
V27
RW
0
V28
R
V29
RW
V30
RW
V31
RW
0
V32
R
V33
RW
V34
RW
V35
RW
0
V36
R
V37
RW
V38
RW
V39
RW
0
V151 W
0
V152 RW(e) 0=enable loading of default values
0
V155 RW(e) 0...1023
0
V156 RW(e) 0...1023
0
V157 RW(e) 0...1023
0
V158 RW(e) 0...2047
1...7
V155 RW(e) 0...2047
8...17
V155 RW(e) 0...15
0
V165 W
0
V169 R
0
V200 RW(e) 1...254
0
V201 RW(e) 4800, 9600
0
V205 R
0
F
R
0
L
R
0
B
R
0
C
R
0
C
W
0
T
RW
The event register can be read by the L com-
mand only once. Should a fault occur e.g. in the
data transfer, it is possible, by using the B
command, to re-read the contents of the event
register. When required, the B command can be
repeated.
Values
0...999
0...999
0...999
0...999
0...999
0...999
0...999
0...999
0...999
0...999
0...999
0...999
0...999
0...999
0...999
1=storing, takes about 5 s
1=inhibit loading of default values
0=reset
1=activate
Fault code
E.g. 055 M
SPTO 6D3
Time, channel number and
event code
Time, channel number and
event code
0=normal state
1=module been subject to
automatic reset
2=overflow of event register
3=events 1 and 2 together
0=resetting
0.000...59.999 s
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

Spac 636 c

Table of Contents