44
Data
Setting/run mode selection
Interlocking selection
Interlocking program
Event delay; —>10 (open)
Event delay; —>01 (close)
Event delay; —>11
Event delay; —>00
Use of input 10
Use of input 11
Use of input 14
Operation direction of inputs 8...17
Signal output activation by inputs 8...17
Operation of OPEN and CLOSE
outputs by inputs 8...17
Memory controlled function of the
indicators of the binary inputs
Event delay; —>activated
Event delay; —>reset
Event reporting
Load default values after EEPROM failure
Event mask
Event mask
Event mask
Event mask
Event mask
Event mask
Data communication address
Data transfer rate
Channel Code
Default value
0
S198
0=setting mode
0
S199
1= interlockings in use
0
M200
END
:
M300
1...7
S10
0.0 s
1...7
S11
0.0 s
1...7
S12
0.2 s for CB and
10.0 s for non CB
1...7
S13
0.2 s for CB and
10.0 s for non CB
10
S1
0=general mode
11
S1
0=general mode
14
S1
0=general mode
8...17
S2
1=active at high state
8...17
S3
0=no signal output
8...17
S4
0=no activation or inhibit
8...13
S5
0=not memory controlled
8...17
S10
0.0 s
8...17
S11
0.0 s
1...17
S20
0=event reporting enabled
0
V152
1=inhibited
0
V155
67
0
V156
99
0
V157
99
0
V158
1795
1...7
V155
1875
8...17
V155
3
0
V200
99
0
V201
9600