ABB SPAC 536 C User Manual page 72

Feeder terminal
Table of Contents

Advertisement

40
Data
Operation of OPEN and CLOSE 8...17
outputs via inputs 8...17
Memory controlled function of
the indicators of the binary inputs
Event delay; —>activated
Event delay; —>reset
Event reporting
Active power (MW)
Reactive power (Mvar)
Active energy (kWh)
Position of local/remote key switch
Active energy (kWh)
Active energy (MWh)
Active energy (GWh)
Active energy; reversed (kWh)
Active energy; reversed (MWh)
Active energy; reversed (GWh)
Reactive energy (kvarh)
Reactive energy (Mvarh)
Reactive energy (Gvarh)
Reactive energy; reversed (kvarh)
Reactive energy; reversed (Mvarh)
Reactive energy; reversed (Gvarh)
Total number of AR cycles 1
No. of AR cycles 1 initiated by AR1 0
No. of AR cycles 1 initiated by AR2 0
No. of AR cycles 1 initiated by AR3 0
Total number of AR cycles 2
Channel Code
Data
direction
S4
RW(e) 0=no activation or inhibit
8...13
S5
RW(e) 0=not memory controlled
8...17
S10
RW(e) 0.0, or 0.1...60.0 s
8...17
S11
RW(e) 0.0, or 0.1...60.0 s
1...17
S20
RW(e) 0=event reporting enabled
0
V3
R
0
V4
R
0
V5
RW
0
V6
R
0
V8
RW
0
V9
RW
0
V10
RW
0
V11
RW
0
V12
RW
0
V13
RW
0
V14
RW
0
V15
RW
0
V16
RW
0
V17
RW
0
V18
RW
0
V19
RW
0
V20
R
V21
RW
V22
RW
V23
RW
0
V24
R
Values
20 = activate OPEN1 output
21 = activate CLOSE1 output
22 = activate OPEN2 output
23 = activate CLOSE2 output
24 = activate OPEN3 output
25 = activate CLOSE3 output
26 = activate OPEN4 output
27 = activate CLOSE4 output
28 = activate OPEN5 output
29 = activate CLOSE5 output
30 = activate OPEN6 output
31 = activate CLOSE6 output
120 = inhibit OPEN1 output
121 = inhibit CLOSE1 output
122 = inhibit OPEN2 output
123 = inhibit CLOSE2 output
124 = inhibit OPEN3 output
125 = inhibit CLOSE3 output
126 = inhibit OPEN4 output
127 = inhibit CLOSE4 output
128 = inhibit OPEN5 output
129 = inhibit CLOSE5 output
130 = inhibit OPEN6 output
131 = inhibit CLOSE6 output
1=memory controlled
1=event reporting inhibited
-999.99...+999.99 MW
-999.99...+999.99 Mvar
0...999999999 kWh
0=local
1=remote
0...999 kWh
0...999 MWh
0...999 GWh
0...999 kWh
0...999 MWh
0...999 GWh
0...999 kvarh
0...999 Mvarh
0...999 Gvarh
0...999 kvarh
0...999 Mvarh
0...999 Gvarh
0...999
0...999
0...999
0...999
0...999